1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
54/105
5.
To exit the COEn function push MENU key or wait the timeout.
17.10 R
EAD
-
OUT OF A COMPRESSOR
N
OT ENABLED
During the normal running condition a disabled compressor is displayed with a blinking label alternated with the measurement value of
the display.
If the compressor is disabled these the corresponding labels: C1dS = compressor 1 disabled…C6dS = compressor 6 disabled
The label C1dS…C6dS are available only if the corresponding compressor is configured.
17.11 R
EAD
-
OUT OF THE COMPRESSOR DISCHARGE TEMPERATURE PROBE
The menu function allows to read-out the compressor temperature probes.
COdt FUNCTION
shows the discharge temperatures
Label involved in
Codt
function:
CO1t
Compressor 1 discharge temperature…
CO6t
Compressor 6 discharge temperature
1. Use
the
UP
or
DOWN
keys to select
COdt
2. Push SET key: bottom display =
CO1t
, top display = temperature value of that probe.
3. Use the UP or DOWN kys to scroll the list:
CO1t
or
CO2t
or
CO3t
or
CO4t
or
CO5t
or
CO6t
4. To exit the COEn function push MENU key or wait the timeout
ATTENZIONE
The labels
Codt
are available only if the corresponding compressor probe is configured.
The display resolution is 0.1°C until the read-out is 99.9, over 100°C it is 1°C.
17.12 R
EAD
-
OUT OF THE RUNNING HOURS
This menu allows to shows all the time running hours of the compressors, supply fan and pumps.
Hour FUNCTION
to show the controlled load consumption
Label involved in the Hour function:
CO1H
Compressor 1 running hours .. CO6H Compressor 6 running hours.
EP1H
Evaporator water pump or Supply fan running hours (air/air)
EP2H
Support evaporator water pump running hours
CP1H
Condenser water pump running hours
CP2H
Support condenser water pump running hours
The labels are displayed only if the corresponding output is present and configured.
The running hours is displayed on the top display, the resolution is x 10 hours (eg 2 means 20 hours, 20 means 200hours)
Enter the function Menu
1.
Use the UP or DOWN keys to select
Hour
2.
Push SET key: bottom display = above labels, top display = hours x10. The time
is on.
3.
Use the UP or DOWN keys to scroll the list.
4.
To exit the Hour function push MENU key or wait the timeout
17.13 R
ESET THE RUNNING HOUR
Enter the function Menu
1.
Within the Hour function select, with UP or DOWN, the interested label: CO1H, CO2H, CO3H, CO4H, CO6H, EP1H, EP2H, CP1H,
CP2H.
2. Push
the
SET
keys for 3seconds: the top display shows the running hours blinking value, then it shows 0 to confirm the reset. The
next load label is automatically loaded.
To exit the Hour function push MENU key or wait the timeout
17.14 R
EAD
-
OUT OF THE COMPRESSOR STARTS
-
UP
For each compressor is possible to show the number of starts-up.
COSn FUNCTION:
number of starts-up of the compressor
Label involved in COSn function:
C1S
number of compressor 1 starts-up ..
C6S
number of compressor 6 starts-up
The labels are displayed only if the corresponding output is present and configured
The number of starts-up is displayed on the top display, the resolution is x 10 (eg 2 means 20 starts, 20 means 200starts)
Enter the function Menu
1.
Use the UP or DOWN keys to select
COSn
.
2. Push
SET
one time: the label of the first load C1S is showed on the top display, the bottom display shows the number x10.
3.
With UP or DOWN scroll the compressor list.
4.
To exit the Hour function push MENU key or wait the timeout
17.15
R
ESET THE STARTS
-
UP NUMBER
Enter the function Menu
1.
Within the Hour function select, with UP or DOWN, the interested label: CS1, CS2, CS3, CS4, CS6.
2. Push
the
SET
keys for 3seconds: the top display shows the running hours blinking value, then it shows 0 to confirm the reset. The
next load label is automatically loaded.
3.
To exit the Hour function push MENU key or wait the timeout.
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...