36 LOAD MAINTENANCE
PARAMETERS CO26..CO31
are the set of the running hour counters of the compressors.
They establish, for each load, the number of running hours limit to display a maintenance message.
If one of these parameters is equal to 0 the maintenance signalling is disabled but the running hours counter remains active.
36.1 C
OMPRESSOR MAINTENANCE RESQUESTS
Label description
ACP1 (
maintenance comp
. 1) –…ACP6 (
maintenance comp
. 6)
Activation
Compressor running hours > counter setpoint for that compressor
Reset
Running hour reset (Hour label in Menu function)
Restart
Manual
Icon
blinking
Actions
Alarm relay and buzzer activated
REGULATIONS
Actions
Only signalling
Loads
Not modified
The parameters
CO32 / CO33
define the hour set counters for the evaporator water pump / Support
evaporator water pump / Supply fan.
They establish the load running hours limit of the pump/s or the supply fan to give a maintenance signalling. If one of these parameters
is equal to 0 the maintenance signalling of that load is disabled but the running hours counter remains active.
37 CONDENSER FAN REGULATION
The
FA01
and
FA02
parameters define the operative mode of the condenser fans. The CF68 and CF69 selects which are the output
signals.
Par.
CF68
Condenser fan control signal of the circuit #1
0= 0 ÷10V
1= 4÷20mA
2= PWM
Par.
CF69
Condenser fan control signal of the circuit #2
0= 0 ÷ 10V
1= 4÷20mA
2= PWM
Par.
FA01
Fan regulation
0 = Output not enabled
1 = always on
2 = ON/OFF step regulation
3 = ON/OFF continuous step regulation
4 = proportional fan speed
Par.
FA02
Fan operative mode
0 = Fan on only if compressor on
1 = Independent from the compressor, off during the stand–by / or from remote OFF
Parameter combination
FA01 – FA02
Par.
FA01
=
1
+ Par.
FA02 = 0
Fans on when the compressor on (the fans work following the same output algorithm)
Par.
FA01
=
1
+ Par.
FA02 = 1
Independent from the compressor status but off in stand–by.
Par.
FA01
=
2
+ Par.
FA02
=
0
Fans on, with ON/OFF regulation and with temperature/pressure transducer control, only when the compressor is on (at least one relay
is configured as fan control). When the compressor turns off also the fans are forced off.
Par.
FA01
=
2
+ Par.
FA02
=
1
Fans on, with ON/OFF regulation and with temperature/pressure transducer control, only when the compressor is on (at least one relay
is configured as fan control). When the compressor turns off the fans are thermoregulated depending on the condensing
temperature/pressure.
Par.
FA01
=
3
+ Par.
FA02
=
0
Fans on, with ON/OFF continuos regulation and with temperature/pressure transducer control, only when the compressor is on (at least
one relay is configured as fan control). When the compressor turns off also the fans are forced off.
Par.
FA01
=
3
+ Par.
FA02
=
1
Fans on, with ON/OFF continuos regulation and with temperature/pressure transducer control, only when the compressor is on (at least
one relay is configured as fan control). When the compressor turns off the fans are thermoregulated depending on the condensing
temperature/pressure.
Par.
FA01
=
4
+ Par.
FA02
=
0
Fans on, with proportional regulation (PWM, 4..20mA, 0.10V) and with temperature/pressure transducer control, only when the
compressor is on. When the compressor turns off also the fans are forced off.
Par.
FA01
=
4
+ Par.
FA02
=
2
Fans on, with proportional regulation (PWM, 4..20mA, 0.10V) and with temperature/pressure transducer control, only when the
compressor is on. When the compressor turns off the fans are thermoregulated depending on the condensing temperature/pressure.
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...