1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
38/105
Ar 6
Antifreeze alarm probe / heaters / appoggio in Chiller mode.
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
0 3
Ar 7
Antifreeze alarm probe / heaters / support heaters in HP mode.
0= Not enabled
1= Evaporator inlet.
2= Evaporator outlet 1 and 2.
3= Evaporator outlet 1 and 2 and common outlet.
0 3
Ar 8
Thermoregulation probe for anti-freeze alarm / condenser heaters.
0= not enabled.
1= Condenser common water inlet probe.
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet.
0 4
Ar 9
Anti-freeze heaters or condenser/evaporator water pump control with unit in
remote OFF or stand-by mode:
0= Control not enable
1=Controlled by anti-freeze thermoregulation.
0 1
Ar 10
Anti-freeze heaters control for condenser/evaporator faulty probe:
0= Anti-freeze heaters OFF
1= Anti-freeze heaters ON
0 1
Boiler function
Ar 11
Boiler function
0=Not enabled
1=Enabled for integration heating
2= Enabled for heating
0 2
Ar 12
External air temperaure setpoint for boiler heaters (on)
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 13
Temperature differential for boiler heaters (off)
0
0
25.0
45
°C
°F
Dec
int
Ar 14
Time delay before turning the boiler on
0
250
Min
Boiler function in Chiller mode
Ar 15
Setpoint for boiler heaters (on) in chiller
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 16
Proportional band for boiler heaters in chiller
-30.0
-22
70.0
158
°C
°F
Dec
int
Boiler function in heat pump
Ar 17
Setpoint for boiler heaters (on) in HP
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 18
Proportional band for boiler heaters in HP
0.1
0
25.0
45
°C
°F
Dec
int
Ar 19
External air setpoint to stop the compressor as integration function
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 20
External air differential to stop the compressor as integration function
0.1
0
25.0
45
°C
°F
Dec
int
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Defrost
Parameter
Description
min
max
udm
Risoluzione
dF 1
Defrost configuration:
0= Not enabled
1= Temperature / pressure
2= start depends on par. dF24 stop for time duration
3= start depends on par. dF24 stop for external contact
0 3
dF 2
Temperature or pressure of the defrost start-up
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 3
Temperature or pressure of the defrost stop
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 4
Minimum defrost duration.
0
250
Sec
dF 5
Maximum defrost duration.
1
250
Min
dF 6
Time delay between the defrost of two circuits
0
250
Min
dF 7
OFF compressor delay before the defrost
0
250
Sec
dF 8
OFF compressor delay after the defrost
0
250
Sec
dF 9
Defrost interval time of the same circuit
1
99
Min
dF 10
Temperature setpoint for combined defrost of the 1
st
circuit after parameter
DF10 counting.
-30.0
-22
70.0
158
°C
°F
Dec
int
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...