1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
23. Temperature
probe
NTC
for auxiliary output #2
24. Temperature
probe
NTC
for condensing circuit #1
25. Temperature
probe
NTC
for condensing circuit #22
After the number 25 the display configuration can be selected from
o 1
to
c62
that allows to set an analogue input as digital input (see
polarity of the digital input/outputs).
8.2 A
NALOG INPUT
C
ONFIGURATION
P
B
3 - P
B
4 - P
B
5 - P
B
6
Parameter involved:
CF10 =
Configuration PB3
CF11 =
Configuration PB4
CF12 =
Configuration PB5
CF13 =
Configuration PB6
0 Not
enabled
1 Temperature
probe
PTC
for compressor 1 discharge
2 Temperature
probe
PTC
for compressor 2 discharge
3 Temperature
probe
PTC
for compressor 3 discharge
4 Temperature
probe
PTC
for compressor 4 discharge
5 Temperature
probe
PTC
for compressor 5 discharge
6 Temperature
probe
PTC
for compressor 6 discharge
7 Temperature
probe
NTC
for evaporator inlet
8 Temperature
probe
NTC
for evaporator outlet # 1
9 Temperature
probe
NTC
for evaporator outlet # 2
10 Temperature
probe
NTC
for common evaporator outlet
11 Temperature
probe
NTC
for common hot water condenser / recovery inlet
12 Temperature
probe
NTC
for hot water condenser / recovery inlet circuit #1
13 Temperature
probe
NTC
for hot water condenser / recovery inlet circuit #2
14 Temperature
probe
NTC
for hot water condenser / recovery outlet circuit #1
15 Temperature
probe
NTC
for hot water condenser / recovery outlet circuit #2
16 Temperature
probe
NTC
for hot water condenser / recovery common outlet circuit
17 Temperature
probe
NTC
for free cooling water inlet
18 Temperature
probe
NTC
for free cooling external air
19 Temperature
probe
NTC
for external air dynamic setpoint/ boiler / change over
20 Temperature
probe
NTC
for combined defrost circuit #1
21 Temperature
probe
NTC
for free cooling water inlet #2
22 Temperature
probe
NTC
for auxiliary output #1
23 Temperature
probe
NTC
for auxiliary output #2
24
Condenser probe circuit 1 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
25
Condenser probe circuit 2 ( temperature
NTC
/ pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
26
Evaporator pressure probe circuit 1 (pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
27
Evaporator pressure probe circuit 1 (pressure
4÷20 mA
/ ratio-metric
0÷ 5Volt
)
28
Auxiliary output 1 pressure probe control (
4÷20 mA
/ ratio-metric
0÷ 5Volt).
29
Auxiliary output 2 pressure probe control (
4÷20 mA
/ ratio-metric
0÷ 5Volt).
30
Dynamic setpoint pressure probe (
4÷20 mA)
After the number 30 the display read-out goes from “
o 1”
to “
c62”
that allows to set an analogue input as digital input (see polarity input
of digital inputs).
8.3 D
IGITAL
I
NPUT
C
ONFIGURATION
I
D
1 – I
D
18
Parameters involved:
CF36 =
Configuration ID1…
CF53 =
Configuration ID18
0. Not
enabled
1.
Remote ON / OFF
2.
Remote chiller / heat pump
3.
Flow switch/ Supply fan overload
4.
Flow switch of heated side
5.
Antifreeze heater circuit 1
6.
Antifreeze heater circuit 2
7.
High pressure switch circuit # 1
8.
High pressure switch circuit 2
9.
Low pressure switch circuit 1
10. Low pressure switch circuit 2
11. Compressor 1 high pressure
12. Compressor 2 high pressure
13. Compressor 3 high pressure
14. Compressor 4 high pressure
15. Compressor 5 high pressure
16. Compressor 6 high pressure
17. Compressor 1 overload
18. Compressor 2 overload
19. Compressor 3 overload
20. Compressor 4 overload
21. Compressor 5 overload
22. Compressor 6 overload
23. Condenser fan overload of circuit 1
24. Condenser fan overload of circuit 2
25. Condenser fan overload of circuit 1 and 2 (comun)
Содержание ichill IC260L
Страница 1: ...IC200L Series User manual dIXEL ...
Страница 7: ......
Страница 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Страница 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Страница 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...