1592017050  XLR470 GB r1.0 24.05.07.doc 

XLR470 

11/18 

9.

 

DIGITAL INPUTS 

The  instrument  can  support  up  to  2  free  contact  digital  inputs.  Both  of  them  can  be  configured  as  One  is  always  configured  as  door  switch,  the 
second is programmable in seven different configurations by the “

I2F

” parameter. 

1.14

 

DOOR SWITCH INPUT  (MP1, MP2, MP) 

It signals the door status to the controller: 

MP1

:  door open for section  1; 

MP2

:  door open for section  2; 

MP

 door open for both the sections.  

When the door is open the status of compressor (and fans) depends on the “

odc1

” and  “

odc2

”parameters: 

no

 = normal (no changes); 

Fan

 = Fan 

OFF  (if  fan  is  present); 

CPr

  =  Compressor  OFF; 

F_C

  =  Compressor  and  fan  OFF.  Since  the  door  is  opened,  after  the  delay  time  set  through 

parameter  “

doA

”,  the  alarm  output  is  enabled  and  the  display  shows  the  message  “

dA

”.  The  alarm  stops  as  soon  as  the  external  digital  input is 

disabled again. During this time and then for the delay “

dot

” after closing the door, the high and low temperature alarms are disabled. 

1.15

 

CONFIGURABLE INPUT - GENERIC ALARM (EA1, EA2, EAL) 

It signals to the controller: 

EA1

: generic alarm – section 1; 

EA2

: generic alarm – section 2; 

EAL

: generic alarm – it counts for both the sections.  

As soon as the digital input is activated the unit will wait for “

did1

” time for section 1 and “

did2

” time for section 2 delay before signalling the “

EAL

” 

alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-activated. 

1.16

 

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BA1, BA2, BAL) 

It signals to the controller: 

bA1

: serious alarm – section 1; 

bA2

: serious alarm – section 2; 

bAL

: serious alarm – it counts for both the sections.  

As soon as the digital input is activated the unit will wait for “

did1

” time for section 1 and “

did2

” time for section 2 delay before signalling the “

bAL

” 

alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated. 

1.17

 

CONFIGURABLE INPUT - START DEFROST (DF1, DF2, DEF) 

It executes a defrost if there are the right conditions, respectively for: 

dF1

:  section 1; 

dF2

: section 2; 

dEF

: both the sections.  

After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf1” and 
“MdF2” safety time is expired. 

1.18

 

CONFIGURABLE INPUT -  REMOTE ON/OFF (OF1, OF2, ONF) 

This function allows to switch ON and OFF a sections of the instrument or the whole instrument according to the following setting: 

oF1

:  section  1;   

oF2

: section 2; 

onF

: it counts for both the sections. When the digital input is de-activated, the corresponding section restarts working. 

1.19

 

CONFIGURABLE INPUT - ENERGY SAVING (ES) 

The Energy Saving function allows to change the set point value as the result of the SET1+HES1 for section and SET2 + HES2 fro section 2. This 
function is enabled until the digital input is activated. 

1.20

 

DIGITAL INPUTS POLARITY  

The digital inputs polarity depends on “

I1P

” and “

I2P

” parameters: 

CL

 : the digital input is activated by closing the contact; 

  OP

  :  the  digital  input  is 

activated by opening the contact 

10.

 

INSTALLATION AND MOUNTING 

The  temperature  range  allowed  for  correct  operation  is  0  -  60  °C.  Avoid  places  subject  to  strong  vibrations,  corrosive  gases,  excessive  dirt  or 
humidity. The same recommendations apply to probes. Let the air circulate by the cooling holes. Thanks to the case, 

XLR470 

model can be panel or 

wall mounted. See the following instructions for details. 

A

B

C

D

E

G

F

 

FIG. 1

 

A

B

C

G

F

D

 

 

FIG. 2 

 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: