dixell COOL MATE XLR470 Скачать руководство пользователя страница 9

dIXEL

dIXEL

dIXEL

dIXEL

    

Operating manual 

cod. 1592

cod. 1592

cod. 1592

cod. 1592017

017

017

017050

050

050

050    

 

1592017050  XLR470 GB r1.0 24.05.07.doc 

XLR470 

9/18 

FnC2   Fan operating mode, section 2

C-n

 = running with the compressor 2, OFF during the defrost; 

C-y

 = running with the compressor 2, ON 

during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd2    Fan delay after defrost, section 2:

 (0÷255 min)

 

The time interval between the defrost end and evaporator fans start.

 

FSt2 

Fan stop temperature, section 2:

 (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe 2, above which the fan is 

always OFF. 

FAP2   Probe selection for fans management, section 2: nP 

= no probe: fan follows the setting of FnC1 parameter; 

P1 

= thermostat 1 probe; 

P2 

= evaporator 1probe;

 P3 

= thermostat 2 probe;  

P4 

= evaporator 2probe; 

ALARMS 
ALc1   Temperature alarms configuration, section 1: 

it determines if alarms are relative to set point 1 or referred to absolute values: 

rE

 relative 

to set point; 

Ab 

absolute temperature

  

ALU1    Maximum alarm, section 1:  
 

with ALc1=rE:

 alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the probe values exceeds the “SET1+ALU” value.  

 

with ALc1=Ab: 

absolute alarm, (Set1÷Full Sc.) Maximum alarm is enabled when the probe values exceeds the “ALU” value. 

ALL1    Minimum alarm, section 1:  

 

with ALc1=rE:

 relative to set point1, (0÷50°C)  this value is subtracted from the set point1. The alarm signal is enabled when the probe 

values goes below the “SET1-ALL” value. 

 

with ALc1=Ab

 absolute value, minimum alarm is enabled when the probe values goes below the “ALL1” value. 

ALd1   Temperature alarm delay, section 1:

 (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm 

signalling. 

dAo1   Delay  of  temperature  alarm  at  start-up,  section  1:

  (0min÷23h  50min)  time  interval  between  the  detection  of  the  temperature  alarm 

condition in section after the instrument power on and the alarm signalling.

 

ALc2   Temperature alarms configuration, section 2: 

it determines if alarms are relative to set point 2 or referred to absolute values: 

rE

 relative 

to set point; 

Ab 

absolute temperature 

ALU2    Maximum alarm, section 2

:  

 

with ALc2=rE:

 alarm relative to set point1, (0÷50°C) Maximum alarm is enabled when the probe values exceeds the “SET2+ALU” value.  

 

with ALc2=Ab: 

absolute alarm, (Set2÷Full Sc.) Maximum alarm is enabled when the probe values exceeds the “ALU” value. 

ALL2    Minimum alarm, section 2:  

 

with ALc2=rE:

 relative to set point1, (0÷50°C)  this value is subtracted from the set point2. The alarm signal is enabled when the probe 

values goes below the “SET2-ALL” value. 

 

with ALc2=Ab

 absolute value, minimum alarm is enabled when the probe values goes below the “ALL2” value. 

ALd2   Temperature alarm delay, section 2:

 (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm 

signalling. 

dAo2   Delay  of  temperature  alarm  at  start-up,  section  2:

  (0min÷23h  50min)  time  interval  between  the  detection  of  the  temperature  alarm 

condition in section after the instrument power on and the alarm signalling.

 

AFH 

Temperature alarm and fan differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for temperature alarm set point and fan regulation 

set point, always positive.

 

EdA  

Alarm delay at the end of defrost: 

(0

÷

255 min) Time interval between the detection of the temperature alarm condition at the end of defrost 

and the alarm signalling. 

dot  

Delay of temperature alarm after closing the door : 

(0

÷

255 min) Time delay to signal the temperature alarm condition after closing the 

door. 

doA  

Open door alarm delay:

(0÷255 min) delay between the detection of the open door condition and its alarm signalling: the flashing message 

dA

” is displayed. 

PROBE INPUTS 
Pbc 

Kind of probe

Ptc

 = PTC; ntc = NTC 

oFS1  Thermostat 1 probe calibration (10-11)

: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the thermostat 1 probe. 

oFS2  Evaporator 1 probe calibration (8-9)

: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the evaporator 1 probe. 

oFS3  Thermostat 2 probe calibration (6-7) 

: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the thermostat 2 probe. 

oFS4  Evaporator 2 probe calibration (4-5)

: (-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the evaporator 2 probe. 

P2P 

Evaporator 1 probe presence

 :

 no

= not present: the defrost 1 stops only by time; 

yES=

 present: the defrost 1 stops by temperature. 

P3P 

Thermostat 2 probe presence: no

= not present; 

yES

= present. 

P4P 

Evaporator 2 probe presence

 :

 no

= not present: the defrost 2 stops only by time; 

yES=

 present: the defrost 2 stops by temperature. 

DIGITAL INPUTS 
i1P 

Digital input 1 polarity (1-2): 

 

CL

 : the digital input is activated by closing the contact;

 

 

OP

 : the digital input is activated by opening the contact. 

i1F 

Digital input 1 operating mode(1-2): configure the digital input function

 

MP1

 = door switch 1; 

MP2

 = door switch 2, 

MP

: door switch (it’s used by both the sections); 

EA1 = 

generic alarm section 1; 

EA2 = 

generic 

alarm section 2; 

EAL 

= generic alarm (it’s used by both the sections);  

bA1

 = serious alarm mode section 1;

 bA2

 = serious alarm mode 

section 2; , 

bAL 

= serious alarm mode section (it’s used by both the sections);  

dF1

 = Start defrost, section 1; 

dF2

 = Start defrost, section 2; 

dEF

 =

 

Start defrost (it’s used by both the sections);  

oF1

 = remote on/ off, section1; 

oF2

 = remote on/ off, section 2; 

oFF = 

 = remote on/ off 

(it’s used by both the sections); 

ES

 = Energy Saving

 

i2P 

Digital input 2 polarity(2-3)

 

CL

 : the digital input is activated by closing the contact;

 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: