SECTION 2 

For the 

section 2

 two defrost modes are available through the “

tdF2

” parameter:  

tdF2= rE 

defrost with electrical heater  

tdF2= in

 or hot gas.  

The defrost interval is control by means of parameter “

EdF2

”: 

rtc (only for instruments with RTC): 

beginning of defrost cycles is set by the 

L2d1÷L2d6

 parameters during the working days and 

S2d1÷S2d6

 

during the holidays  

in

 the defrost is made every “

IdF

” time 

Sd

 the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON) 

At the end of defrost the drip time is controlled through the “

Fdt2

” parameter. 

3.

 

RELATION BETWEEN DEFROSTS 

Different kinds of defrosts are available for each section. 
The relation between defrosts is set by the 

dFS 

parameter: 

relation between defrosts

4 relation between the 2 sections of the controller are available, to manage different kinds of applications:  

in 

= independent defrosts;  

StS

 = same defrost start, synchronised defrost end;  

St

 = same defrost start, independent defrost end;  

SE 

=

 

sequential defrost;  

 

 

  dFS= in - independent defrosts  

The defrosts of the 2 sections of controller are completely independent.  

First section: 

defrost interval is set by 

idF1

 parameter. 

Second section: 

defrost interval is set by 

idF2

 parameter. 

The defrost interval is control by means of parameter “

EdF1(2)

”: 

in

 the defrost is made every “

IdF1(2)

” time 

Sd

 the interval “IdF1(2)” is calculate through Smart Defrost algorithm (only when the compressor is ON) 

 

Manual defrost activation, by pushing the DOWN key (defrost 1) or UP key (defrost 2). 
By pushing the Down key or Up key for 3s, a defrost request is generated for section 1 or 2 respectively. The defrost interval is re-loaded.  

 

 

dFS  =  StS  –  Same  defrost  start,  end  defrost  synchronised  or  dFS  =  St  -    Same  defrost  start,  end  defrost 
independent.  

The defrost of the 2 sections of controller starts at the same time. 

idF1 

parameter sets the defrost interval for both the sections. The defrosts are 

performed at regular interval if EdF1 = in or according to the Smartdefrost algorithm if EdF1 = Sd. 

 

With 

dFS = StS

 regulation restarts only when defrost is finished for both the sections. The section that finishes the defrost before the other starts 

dripping time until also the other section has not finished its defrost.

  

Manual defrost activation, by pushing the DOWN key (defrost 1) or UP key (defrost 2). 
By pushing the Down key or Up key for 3s, a defrost request is generated for both the sections 1 and 2. The defrost interval is re-loaded.  

 

 With 

dFS = St

 each section restarts regulation as soon as its defrost is finished.  

 

 

dFS = SE – sequential defrost 

The defrost of 2 sections is synchronised. 

idF1 

parameter sets the defrost interval for both the sections. Defrosts are performed at regular interval if 

EdF1 = in or according to the Smartdefrost algorithm if EdF1 = Sd. Section 1 does its defrost first, at the end of the defrost of section 1, section 2 
starts its defrost.. 
Manual defrost activation, by pushing the DOWN key (defrost 1) or UP key (defrost 2). 
By pushing the Down key or Up key for 3s, a defrost request is generated for both the sections 1 and 2. The defrost interval is re-loaded.  

5.

 

CONTROL OF EVAPORATOR FANS FOR SECTION 1 

Section 1 has 1 relay to control evaporator fan (25-26) 
The fan control mode is selected by means of the “

FnC1

” parameter: 

FnC1=C-n

  

fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

FnC1= O-n

 

 fans will run continuously, but not during defrost  

 

After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd1” parameter. 

FnC1=C-y

  

fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC1=O-y

  

fans will run continuously also during defrost 

 

An additional parameter “

FSt1

” provides the setting of temperature, detected by the evaporator probe, above which the fans are always OFF. This 

can be used to make sure circulation of air only if his temperature is lower than set in “FSt1”. 
 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: