Operating manual
cod. 1592
cod. 1592
cod. 1592
cod. 1592017
017
017
017050
050
050
050
1592017050 XLR470 GB r1.0 24.05.07.doc
XLR470
17/18
Label
Name
Range
Default
level
FSt2
Fans stop temperature, section 2
-50,0÷110°C/ -58÷230°F
-30.0
Pr2
FAP2
Probe for fans 2
P1÷P3
P4
Pr2
ALARM
ALc1
Temperature alarms configuration, section 1
rE / Ab
Ab
Pr2
ALu1
Maximum alarm, section 1
-50,0÷150°C/ -58÷302°F
110
Pr1
ALL1
Minimum alarm, section 1
-50,0÷150°C/ -58÷302°F
-50.0
Pr1
ALd1
Temperature alarm delay, section 1
0÷255 min.
15
Pr2
dAo1
Delay of temp. alarm at start-up, section 1
0 ÷ 23h 50 min.
1.3
Pr2
ALc2
Temp. alarms configuration, section 2
re ÷ Ab
Ab
Pr2
ALu2
Maximum alarm, section 2
-50,0÷150°C/ -58÷302°F
110
Pr1
ALL2
Minimum alarm, section 2
-50,0÷150°C/ -58÷302°F
-50.0
Pr1
ALd2
Temperature alarm delay, section 2
0÷255 min.
15
Pr2
dAo2
Delay of temp. alarm at start-up, section 2
0 ÷ 23h 50 min.
1.3
Pr2
AFH
Temperature alarm and fan differential
0,1÷25,5 °C / 1÷45°F
1.0
Pr2
EdA
Alarm delay at the end of defrost
0÷255 min.
20
Pr2
dot
Delay of temp. alarm after closing the door
0÷255 min.
20
Pr2
doA
Open door alarm delay
0÷254 min., nu
15
Pr2
ANALOGUE INPUTS
Pbc
Kind of probe
PTC/ntc
ntc
Pr2
oFS1
Thermostat1 probe calibration
-12,0÷12,0°C / -21÷21°F
0.0
Pr2
oFS2
Evaporator 1 probe calibration
-12,0÷12,0°C / -21÷21°F
0.0
Pr2
oFS3
Thermostat 2 probe calibration
-12,0÷12,0°C / -21÷21°F
0.0
Pr2
oFS4
Evaporator 2probe calibration
-12,0÷12,0°C / -21÷21°F
0.0
Pr2
P2P
Evaporator 1 probe presence
n / y
Y
Pr2
P3P
Thermostat 2 probe presence
n ÷ y
Y
Pr2
P4P
Evaporator 2 probe presence
n ÷ y
Y
Pr2
DIGITAL INPUTS
I1P
Digital input 1 polarity
cL÷OP
cL
Pr2
i1F
Digital input 1 operating mode
MP1; MP2, MP; EA1; EA2; EAL; bA1; bA2; ,
bAL; dF1; dF2; dEF; oF1; oF2; oFF; ES
EAL
Pr2
i2P
Digital input 2 polarity
cL÷OP
cL
Pr2
i2F
Digital input 2 operating mode
MP1; MP2, MP; EA1; EA2; EAL; bA1; bA2; ,
bAL; dF1; dF2; dEF; oF1; oF2; oFF; ES
EAL
Pr2
odc1
Comp. and fan status when open door, sect 1
no, Fan, CPr, F_C
no
Pr2
rrd1
Outputs restart after door open alarm, sect. 1
n, y
y
Pr2
did1
Time interval delay for digital input alarm, sect. 1
0÷255 min.
5
Pr2
odc2
Comp. status when open door, section 2:
no, Fan, CPr, F_C
no
Pr2
rrd2
Outputs restart after door open alarm, sect. 2
n, y
y
Pr2
did2
Time interval delay for digital input alarm, sect. 2
0÷255 min.
5
Pr2
OTHER
oA6
Auxiliary output configuration
cP1 / cP2 / dF1 / dF2 / Fn1 / Fn2 / Lg1 / Lg2 /
on1 / on2 / db1 / db2 / ALr
ALr
Pr2
tbA
Alarm relay silencing
n – Y
y
Pr1
AoP
Alarm relay polarity
cL - oP
cL
Pr1
HES1
Temp. increase during the Energy Saving cycle, sect. 1
-30÷30°C / -54÷54°F
0
Pr1
HES2
Temp. increase during the Energy Saving cycle, section 2
-30÷30°C / -54÷54°F
0
Pr1
TIME AND WEEKLY HOLIDAYS (ONLY WITH RTC)
Hur
Current hour
0 ÷ 23
0
Pr1
Min
Current minute
0 ÷ 59
0
Pr1
dAY
Current day
Sun ÷ SAt
Sun
Pr1
Hd1
First weekly holiday
Sun ÷ SAt – nu
nu
Pr1
Hd2
Second weekly holiday
Sun ÷ SAt – nu
nu
Pr1
Hd3
Third weekly holiday
Sun ÷ SAt – nu
nu
Pr1
ENERGY SAVING TIMES (ONLY WITH RTC)
ILE
Energy Saving cycle start during workdays
0 ÷ 23h 50 min.
0
Pr2
dLE
Energy Saving cycle length during workdays
0 ÷ 24h 00 min.
0
Pr2
ISE
Energy Saving cycle start on holidays
0 ÷ 23h 50 min.
0
Pr2
dSE
Energy Saving cycle length on holidays
0 ÷ 24h 00 min.
0
Pr2