XLR470 

17/18 

Label 

Name 

Range 

Default 

level 

FSt2 

Fans stop temperature, section 2 

-50,0÷110°C/ -58÷230°F 

-30.0 

Pr2 

FAP2 

Probe for fans 2 

P1÷P3 

P4 

Pr2 

 

ALARM

 

 

 

 

ALc1 

Temperature alarms configuration, section 1 

rE / Ab 

Ab 

Pr2 

ALu1 

Maximum alarm, section 1 

-50,0÷150°C/ -58÷302°F 

110 

Pr1 

ALL1 

Minimum alarm, section 1 

-50,0÷150°C/ -58÷302°F 

-50.0 

Pr1 

ALd1 

Temperature alarm delay, section 1 

0÷255 min. 

15 

Pr2 

dAo1 

Delay of temp. alarm at start-up, section 1 

0 ÷ 23h 50 min. 

1.3 

Pr2 

ALc2 

Temp. alarms configuration, section 2 

re ÷ Ab 

Ab 

Pr2 

ALu2 

Maximum alarm, section 2 

-50,0÷150°C/ -58÷302°F 

110 

Pr1 

ALL2 

Minimum alarm, section 2 

-50,0÷150°C/ -58÷302°F 

-50.0 

Pr1 

ALd2 

Temperature alarm delay, section 2 

0÷255 min. 

15 

Pr2 

dAo2 

Delay of temp. alarm at start-up, section 2 

0 ÷ 23h 50 min. 

1.3 

Pr2 

AFH 

Temperature alarm and fan differential 

0,1÷25,5 °C / 1÷45°F 

1.0 

Pr2 

EdA 

Alarm delay at the end of defrost 

0÷255 min. 

20 

Pr2 

dot 

Delay of temp. alarm after closing the door 

0÷255 min. 

20 

Pr2 

doA 

Open door alarm delay 

0÷254 min., nu 

15 

Pr2 

 

ANALOGUE INPUTS

 

 

 

 

Pbc 

Kind of probe 

PTC/ntc 

ntc 

Pr2 

oFS1 

Thermostat1 probe calibration 

-12,0÷12,0°C / -21÷21°F 

0.0 

Pr2 

oFS2 

Evaporator 1 probe calibration 

-12,0÷12,0°C / -21÷21°F 

0.0 

Pr2 

oFS3 

Thermostat 2 probe calibration 

-12,0÷12,0°C / -21÷21°F 

0.0 

Pr2 

oFS4 

Evaporator  2probe calibration 

-12,0÷12,0°C / -21÷21°F 

0.0 

Pr2 

P2P 

Evaporator 1 probe presence 

n / y

 

Pr2 

P3P 

Thermostat 2 probe presence 

n ÷ y 

Pr2 

P4P 

Evaporator 2 probe presence 

n ÷ y 

Pr2 

 

DIGITAL INPUTS

 

 

 

 

I1P 

Digital input 1 polarity 

cL÷OP 

cL 

Pr2 

i1F 

Digital input 1 operating mode 

MP1; MP2, MP; EA1; EA2; EAL; bA1; bA2; , 

bAL; dF1; dF2; dEF;  oF1; oF2; oFF; ES 

EAL 

Pr2 

i2P 

Digital input 2 polarity 

cL÷OP 

cL 

Pr2 

i2F 

Digital input 2 operating mode 

MP1; MP2, MP; EA1; EA2; EAL; bA1; bA2; , 

bAL; dF1; dF2; dEF;  oF1; oF2; oFF; ES 

EAL 

Pr2 

odc1 

Comp. and fan status when open door, sect 1 

no, Fan, CPr, F_C 

no 

Pr2 

rrd1 

Outputs restart after door open alarm, sect. 1 

n, y 

Pr2 

did1 

Time interval delay for digital input alarm, sect. 1 

0÷255 min. 

Pr2 

odc2 

Comp. status when open door, section 2: 

no, Fan, CPr, F_C 

no 

Pr2 

rrd2 

Outputs restart after door open alarm, sect. 2 

n, y 

Pr2 

did2 

Time interval delay for digital input alarm, sect. 2 

0÷255 min.

 

Pr2 

 

OTHER

 

 

 

 

oA6 

Auxiliary output configuration 

cP1 / cP2 / dF1 / dF2 / Fn1 / Fn2 / Lg1 / Lg2 / 

on1 / on2 / db1 / db2 / ALr

 

ALr 

Pr2 

tbA 

Alarm relay silencing 

n – Y 

Pr1 

AoP 

Alarm relay polarity 

cL - oP 

cL 

Pr1 

HES1 

Temp. increase during the Energy Saving cycle, sect. 1 

-30÷30°C / -54÷54°F 

Pr1 

HES2 

Temp. increase during the Energy Saving cycle, section 2 

-30÷30°C / -54÷54°F 

Pr1 

 

TIME AND WEEKLY HOLIDAYS (ONLY WITH RTC)

 

 

 

 

Hur 

Current hour 

0 ÷ 23 

Pr1 

Min 

Current minute 

0 ÷ 59 

Pr1 

dAY 

Current day 

Sun ÷ SAt 

Sun 

Pr1 

Hd1 

First weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr1 

Hd2 

Second weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr1 

Hd3 

Third weekly holiday 

Sun ÷ SAt – nu 

nu 

Pr1 

 

ENERGY SAVING TIMES (ONLY WITH RTC) 

 

 

 

ILE 

Energy Saving cycle start during workdays 

0 ÷ 23h 50 min. 

Pr2 

dLE 

Energy Saving cycle length during workdays 

0 ÷ 24h 00 min. 

Pr2 

ISE 

Energy Saving cycle start on holidays 

0 ÷ 23h 50 min. 

Pr2 

dSE 

Energy Saving cycle length on holidays 

0 ÷ 24h 00 min. 

Pr2 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...