1.9
HOW TO MOVE A PARAMETER FROM THE “PR2” MENU TO “PR1” AND VICE VERSA.
Each parameter present in “
Pr2
” MENU can be removed or put into “
Pr1
”, user level, by pressing
“SET1 +
n
n
n
n
”
.
In “
Pr2”
when a parameter is present in “
Pr1
” the decimal point LE of the bottom display is on.
1.10
HOW TO CHANGE A PARAMETER
To change a parameter value operates as follows:
Enter the Programming mode
Select the required parameter.
Press the “
SET1
” key and the value starts blinking.
Use “
UP
” or “
DOWN
” to change its value.
Press “
SET1
” to store the new value and move to the following parameter.
TO EXIT
: Press
SET1 +
o
o
o
o
or wait 15s without pressing a key.
NOTE
: the set value is stored even when the procedure is exited by waiting the time-out to expire.
1.11
HOW TO LOCK THE KEYBOARD
Keep pressed for more than 3 s the
o
o
o
o
and
n
n
n
n
keys.
The “
POF
” message will be displayed and the keyboard will be locked. At this point it will be possible only to
see the set points.
If a key is pressed more than 3s the “
POF
” message will be displayed.
1.12
TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the
o
o
o
o
and
n
n
n
n
keys, till the “
Pon
” message will be displayed.
1.13
ON/OFF FUNCTION – HOW TO SWITCH ON AND OFF THE CONTROLLER
By pressing the
or
key the controller is switched OFF. The stand-by function switches OFF all the relays and stops the regulation.
During the stand by if a monitored unit is connected, it does not record the instrument data and alarms
To switch the instrument on again press the
or
key.
NOTE1:
When the instrument is in stand-by, all the relays are under power supply. Don’t connect any loads to the normal closed contact of the
relays.
NOTE2:
With the instrument in stand-by, it’s possible to see and modify the set points and enter the programming mode.
8.
PARAMETER LIST
DIFFERENTIALS
Hy1
Differential1:
(0,1÷25,5°C; 1÷45°F): Intervention differential for set point1, always positive. Compressor1 Cut IN is Set Point Plus
Differential1 (Hy1). Compressor1 Cut OUT is when the temperature reaches the set point1.
Hy2
Differential2:
(0,1÷25,5°C; 1÷45°F): Intervention differential for set point2, always positive. Compressor2 Cut IN is Set Point2 Plus
Differential2 (Hy2). Compressor2 Cut OUT is when the temperature reaches the set point2.
REGULATION – SECTION 1
LS1
Minimum set point1 limit:
(-50,0°C
÷
÷
÷
÷
SET1; -58°F÷SET1) Sets the minimum acceptable value for the set point1.
US1
Maximum set point1 limit:
(SET1
÷
÷
÷
÷
110°C; SET1÷230°F) Set the maximum acceptable value for set point1.
OdS1 Outputs activation delay of section 1 at start up:
(0÷255 min) This function is enabled at the initial start up of the instrument and inhibits
any output activation of the section 1 for the period of time set in the parameter. (Light can work)
AC1
Anti-short cycle delay for compressor1:
(0÷30 min) interval between the compressor1 stop and the following restart.
Con1 Compressor1 ON time with faulty probe1:
(0÷255 min) time during which the compressor1 is active in case of faulty thermostat probe.
With COn=0 compressor1 is always OFF.
COF1 Compressor1 OFF time with faulty probe1:
(0÷255 min) time during which the compressor is off in case of faulty thermostat probe. With
COF=0 compressor is always active.
CH1
Kind of action for section 1: CL
= cooling
; Ht =
heating
REGULATION – SECTION 2
LS2
Minimum set point2 limit:
(-50,0°C
÷
÷
÷
÷
SET2; -58°F÷SET2) Sets the minimum acceptable value for the set point2.
US2
Maximum set point2 limit:
(SET2
÷
÷
÷
÷
110°C; SET2÷230°F) Set the maximum acceptable value for set point2.
OdS2 Outputs activation delay of section 2 at start up:
(0÷255 min) This function is enabled at the initial start up of the instrument and inhibits
any output activation of the section 1 for the period of time set in the parameter.
AC2
Anti-short cycle delay for compressor2:
(0÷30 min) interval between the compressor2 stop and the following restart.
Con2 Compressor2 ON time with faulty probe2:
(0÷255 min) time during which the compressor2 is active in case of faulty thermostat probe.
With COn=0 compressor2 is always OFF.