XLR470 

7/18 

1.9

 

HOW TO MOVE A PARAMETER FROM THE “PR2” MENU TO “PR1” AND VICE VERSA. 

Each parameter present in “

Pr2

” MENU can be removed or put into “

Pr1

”, user level, by pressing 

“SET1 + 

n

n

n

n

.  

In “

Pr2”

 when a parameter is present in “

Pr1

” the decimal point LE of the bottom display is on. 

1.10

 

HOW TO CHANGE A PARAMETER  

To change a parameter value operates as follows: 
Enter the Programming mode  
Select the required parameter. 
Press the “

SET1

” key and the value starts blinking. 

Use “

UP

” or “

DOWN

” to change its value. 

Press “

SET1

” to store the new value and move to the following parameter. 

 

TO EXIT

: Press 

SET1 +

 

o

o

o

o

 or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

1.11

 

HOW TO LOCK THE KEYBOARD 

 

Keep pressed for more than 3 s the 

and 

n

n

n

n

 keys. 

The “

POF

” message will be displayed and the keyboard will be locked. At this point it will be possible only to 

see the set points. 
If a key is pressed more than 3s the “

POF

” message will be displayed. 

1.12

 

TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

n

n

n

 keys, till the “

Pon

” message will be displayed. 

1.13

 

ON/OFF FUNCTION – HOW TO SWITCH ON AND OFF THE CONTROLLER 

By pressing the 

 or 

 key the controller is switched OFF. The stand-by function switches OFF all the relays and stops the regulation. 

During the stand by if a monitored unit is connected, it does not record the instrument data and alarms 

To switch the instrument on again press the 

 or 

 key. 

 

NOTE1:

  When  the  instrument  is  in  stand-by,  all  the  relays  are  under  power  supply.  Don’t  connect  any  loads  to  the  normal  closed  contact  of  the 

relays.  

NOTE2:

 With the instrument in stand-by, it’s possible to see and modify the set points and enter the programming mode. 

8.

 

PARAMETER LIST 

DIFFERENTIALS 
Hy1 

Differential1: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set  point1,  always  positive.  Compressor1  Cut  IN  is  Set  Point  Plus 

Differential1 (Hy1). Compressor1 Cut OUT is when the temperature reaches the set point1. 

Hy2 

Differential2: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set  point2,  always  positive.  Compressor2  Cut  IN  is  Set  Point2  Plus 

Differential2 (Hy2). Compressor2 Cut OUT is when the temperature reaches the set point2. 

REGULATION – SECTION 1 
LS1 

Minimum set point1 limit: 

(-50,0°C

÷

÷

÷

÷

SET1; -58°F÷SET1) Sets the minimum acceptable value for the set point1. 

US1 

Maximum set point1 limit: 

(SET1

÷

÷

÷

÷

110°C; SET1÷230°F) Set the maximum acceptable value for set point1. 

OdS1  Outputs activation delay of section 1 at start up:

 (0÷255 min) This function is enabled at the initial start up of the instrument and inhibits 

any output activation of the section 1 for the period of time set in the parameter. (Light can work) 

AC1 

Anti-short cycle delay for compressor1: 

(0÷30 min) interval between the compressor1 stop and the following restart. 

Con1   Compressor1 ON time with faulty probe1: 

(0÷255 min) time during which the compressor1 is active in case of faulty thermostat probe. 

With COn=0 compressor1 is always OFF. 

COF1   Compressor1 OFF time with faulty probe1: 

(0÷255 min) time during which the compressor is off in case of faulty thermostat probe. With 

COF=0 compressor is always active. 

CH1 

Kind of action for section 1: CL 

= cooling

; Ht =  

heating

 

REGULATION – SECTION 2 
LS2 

Minimum set point2 limit: 

(-50,0°C

÷

÷

÷

÷

SET2; -58°F÷SET2) Sets the minimum acceptable value for the set point2. 

US2 

Maximum set point2 limit: 

(SET2

÷

÷

÷

÷

110°C; SET2÷230°F) Set the maximum acceptable value for set point2. 

OdS2   Outputs activation delay of section 2 at start up:

 (0÷255 min) This function is enabled at the initial start up of the instrument and inhibits 

any output activation of the section 1 for the period of time set in the parameter. 

AC2 

Anti-short cycle delay for compressor2: 

(0÷30 min) interval between the compressor2 stop and the following restart. 

Con2   Compressor2 ON time with faulty probe2: 

(0÷255 min) time during which the compressor2 is active in case of faulty thermostat probe. 

With COn=0 compressor2 is always OFF. 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: