HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically  the  parameter  list  of  the 

“Hot  Key”

  is  downloaded  into  the  Controller  memory, the “

doL

” message is blinking followed a by 

flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or 

remove the “

Hot key

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message 

Cause 

Outputs 

“P1” 

Thermostat1 probe failure 

Alarm output ON; Compressor1 output according to parameters “COn1” and “COF1” 

“P2” 

Evaporator 1 probe failure 

Alarm output ON; Other outputs unchanged 

“P3” 

Thermostat 2 probe failure 

Alarm output ON; Compressor2 output according to parameters “COn2” and “COF2” 

“P4” 

Evaporator 2 probe failure 

Alarm output ON; Other outputs unchanged 

“HA” 

High temperature alarm 

Outputs unchanged 

“LA” 

Low temperature alarm 

Outputs unchanged 

“EE” 

Some memory problems 

Alarm output ON; Other outputs OFF 

“dA” 

Door switch alarm 

Outputs unchanged 

“EAL” 

External alarm 

Outputs unchanged 

“bAL” 

Serious external alarm 

Regulation outputs deactivated 

“rtc” 

RTC data wrong 

Outputs unchanged 

“rtF” 

RTC failure 

Outputs unchanged 

“noP” 

Display probe not present 

 

“POF” 

Keyboard locked 

Outputs unchanged

 

“POn” 

Keyboard unlocked 

Outputs unchanged 

 

The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. To reset the “EE” alarm and restart 
the normal functioning press any key, the “

rSt

” message is displayed for about 3s. 

1.26

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer can be silenced by pressing any key.  

1.27

 

 “EE” ALARM 

The 

dIXEL

 instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a failure in the memory data occurs. In 

such cases the alarm output is enabled. 

1.28

 

ALARM RECOVERY 

Probe alarms : “

P1

” (probe1 faulty), “

P2

” “

P3

” and 

“P4”

; they automatically stop 10s after the probe restarts normal operation. Check connections 

before replacing the probe. Door switch alarm “

dA

”  stop as soon as the door is closed. External alarms “

EAL

”, “

bAL

”  stop as soon as the external 

digital input is disabled. The alarm message is displayed until the alarm condition is recovery. All the alarm messages are showed alternating with 
the room temperature except for the “P1” which is flashing. 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: