XLR470 

8/18 

COF2   Compressor2 OFF time with faulty probe2: 

(0÷255 min) time during which the compressor is off in case of faulty thermostat probe. With 

COF=0 compressor2 is always active. 

CH2 

Kind of action for section 2

CL

 = cooling; 

Ht

 =  heating 

DISPLAY 
CF 

Temperature measurement unit:

 °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the SET point and the values  of 

some parameters have to be modified. 

rES 

Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

Lod1   Bottom  display  visualization  (section  1): 

select  which  probe  is  displayed  by  the  instrument  in  the  bottom  display:

  P1

  =  Thermostat  1 

probe; 

P2

 = Evaporator 1 probe; 

P3

 = Thermostat2 probe; 

P4

 = Evaporator 2 probe 

Lod2   Upper display visualization (section 2): 

select which probe is displayed by the instrument in the upper display:

 P1

 = Thermostat 1 probe; 

P2

 = Evaporator 1 probe; 

P3

 = Thermostat2 probe; 

P4

 = Evaporator 2 probe 

DEFROST 
dFS 

Relation between defrosts.

4 relation between the 2 sections of the controller are available, to manage different kinds of applications: 

in 

independent defrosts; 

StS

 = same defrost start, synchronised defrost end; 

St

 = same defrost start, independent defrost end; 

SE 

=

 

sequential 

defrost;  

tdF1   Defrost type, section 1: rE

 = electrical heater (Compressor OFF); 

in

 = hot gas (Compressor and defrost relays ON) 

EdF1  Defrost mode, section 1: in

 = 

interval mode

. The defrost starts when the time “

IdF1

” is expired.  

Sd

  = 

Smartdefrost  mode

.  The  time  IdF  (interval  between  defrosts)  is  increased  only  when  the  compressor  is  running  (even  non 

consecutively);  

rtc  (only  for  instruments  with  RTC): 

beginning  of  defrost  cycles  is  set  by  the 

L1d1÷L1d6

  parameters  during  the  working  days  and 

S1d1÷S1d6

 during the holidays  

SdF1  Set point for SMARTDEFROST, section 1

: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the IdF counting (interval between 

defrosts) in SMARTDEFROST mode. 

dtE1   Defrost termination temperature, section 1:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets the 

temperature measured by the evaporator probe which causes the end of defrost. 

IdF1 

Interval between defrosts, section 1: 

(1÷120h) Determines the time interval between the beginning of two defrost cycles. 

MdF1    (Maximum) duration of defrost, section 1: 

(0÷255 min) When 

P2P = no

, no evaporator probe, it sets the defrost duration, when 

P2P = 

yES

, defrost end based on temperature, it sets the maximum length for defrost. 

tPF1 

Pre-defrost time:

 (0÷30min) The compressor is activated for this time before a hot gas defrost. 

Fdt1   Drain down time, section 1:

 (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control’s 

normal operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.

 

dPo1    First defrost after start-up, section 1

:  

y

 = Immediately; 

n

 = after the IdF time 

tdF2   Defrost type, section 2: rE

 = electrical heater (Compressor OFF); 

in

 = hot gas (Compressor and defrost relays ON) 

EdF2  Defrost mode, section 2: in

 = 

interval mode

. The defrost starts when the time “

IdF1

” is expired.  

Sd

  = 

Smartdefrost  mode

.  The  time  IdF  (interval  between  defrosts)  is  increased  only  when  the  compressor  is  running  (even  non 

consecutively);  

rtc  (only  for  instruments  with  RTC): 

beginning  of  defrost  cycles  is  set  by  the 

L1d1÷L1d6

  parameters  during  the  working  days  and 

S1d1÷S1d6

 during the holidays  

SdF2  Set  point  for  SMARTDEFROST,  section  2

:  (-30

÷

30  °C/  -22

÷

86  °F)  evaporator  temperature  which  allows  the  IdF2  counting  (interval 

between defrosts) in SMARTDEFROST mode. 

dtE2   Defrost termination temperature, section 2:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets the 

temperature measured by the evaporator probe which causes the end of defrost. 

IdF2 

Interval between defrosts, section 2: 

(1÷120h) Determines the time interval between the beginning of two defrost cycles. 

MdF2    (Maximum) duration of defrost, section 2

: (0÷255 min) it sets the defrost duration. 

tPF2 

Pre-defrost time:

 (0÷30min) The compressor 2 is activated for this time before a hot gas defrost. 

Fdt2   Drain down time, section 2:

 (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control’s 

normal operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.

 

dFd  

Display during defrost

rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label; 

 dEG

 = “dEG” 

label; 

dAd  

Defrost display time out:

 (0

÷

255 min) Sets the maximum time between the end of defrost and the restarting of the real room temperature 

display. 

dSd  

Start defrost delay 

: ( 0÷99min) This is useful when different defrost start times are necessary to avoid overloading the plant.  

 

FANS – Section 1 
FnC1   Fan  operating  mode,  section 1

C-n

 = running with the compressor1, OFF during the defrost; 

C-y

 = running with the compressor1, ON 

during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

Fnd1    Fan delay after defrost, section 1:

 (0÷255 min)

 

The time interval between the defrost end and evaporator 1 fans start.

 

FSt1 

Fan stop temperature, section 1:

 (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe, above which the fan is 

always OFF. 

FAP1   Probe selection for fans management, section 1: nP 

= no probe: fan follows the setting of FnC1 parameter; 

P1 

= thermostat 1 probe; 

P2 

= evaporator 1probe;

 P3 

= thermostat 2 probe;  

P4 

= evaporator 2probe; 

FANS – Section 2 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: