DEFAULT SETTING VALUES
Label
Name
Range
Default
level
REGULATION
Set1
Set point 1
LS1÷US1
-5.0
- - -
Set2
Set point 2
LS2÷US2
3.0
- - -
Hy1
Differential 1
0,1÷25,5 °C / 1÷45°F
2.0
Pr1
Hy2
Differential 2
0,1÷25,5 °C / 1÷45°F
2.0
Pr1
REGULATION – SECTION 1
LS1
Minimum set point1 limit
-50,0°C÷SET1 / -58°F÷SET1
-50.0
Pr2
US1
Maximum set point1 limit
SET1 ÷ 150°C / SET1 ÷ 302°F
110
Pr2
odS1
Outputs activation delay of sect. 1 at start up
0÷255 min.
0
Pr2
Ac1
Anti-short cycle delay for compressor1
0÷30 min.
1
Pr1
con1
Compressor1 ON time with faulty probe1
0÷255 min.
15
Pr2
coF1
Compressor1 OFF time with faulty probe1
0÷255 min.
15
Pr2
cH1
Kind of action for section 1
cL / Ht
cL
Pr2
REGULATION – SECTION 2
LS2
Minimum set point2 limit
-50,0°C÷SET2 / -58°F÷SET2
-50.0
Pr2
US2
Maximum set point2 limit
SET2 ÷ 150°C / SET2 ÷ 302°F
110
Pr2
odS2
Outputs activation delay of sect. 2 at start up
0÷255 min.
0
Pr2
Ac2
Anti-short cycle delay for compressor2
0÷30 min.
1
Pr1
con2
Compressor2 ON time with faulty probe2
0÷255 min.
15
Pr2
coF2
Compressor2 OFF time with faulty probe2
0÷255 min.
15
Pr2
cH2
Kind of action for section 2
cL / Ht
cL
Pr2
DISPLAY
cF
Temperature measurement unit
°C / °F
°C
Pr2
rES
Resolution (for °C
in ÷ de
dE
Pr1
Lod1
Bottom display visualization
P1 ÷ P4
P1
Pr2
Lod2
Upper display visualization
P1 ÷ P4
P3
Pr2
DEFROST
dFS
Relation between defrosts
ind; StS; Sti, SE
ind
Pr2
tdF1
Kind of defrost section 1
rE, in
rE
Pr2
EdF1
Defrost mode, section 1
In, Sd,RTC
in
Pr2
SdF1
Set point for Smart Defrost section 1
-30 ÷ +30°C / -22÷+86°F
0
Pr2
dtE1
End defrost temperature section 1
-50,0÷110°C/ -58÷230°F
8.0
Pr2
idF1
Interval between defrosts, section 1
1÷120ore
6
Pr1
MdF1
Maximum duration of defrost, section 1
0÷255 min.
20
Pr1
tPF1
Pre-defrost compressor on time
0÷30 min.
0
Pr2
Fdt1
Dripping time section 1. 1
0÷60 min.
0
Pr2
dPo1
Defrost at power on section . 1
n ÷ y
n
Pr2
tdF2
Kind of defrost section 2
rE, in
rE
Pr2
EdF2
Defrost mode, section 2:
In, Sd, RTC
in
Pr2
SdF2
Set point for Smart Defrost section 2
-30 ÷ +30°C / -22÷+86°F
0
Pr2
dtE2
End defrost temperature section 2
-50,0÷110°C/ -58÷230°F
8.0
Pr2
idF2
Interval between defrosts, section 2
1÷120ore
6
Pr1
MdF2
(Maximum) duration of defrost, section 2
0÷255 min.
20
Pr1
tPF2
Pre-defrost compressor 2 on time
0÷30 min.
0
Pr2
Fdt2
Dripping time section 2
0÷60 min.
0
Pr2
dPo2
Defrost at power on section 2
n ÷ y
n
Pr2
dFd
Display during defrost
rt, it, SEt, dEF, dEG
it
Pr2
dAd
Defrost display time out
0÷255 min.
20
Pr2
dSd
Defrost delay
0÷255 min.
0
Pr2
FANS
FnC1
Fans operating mode, section 1
C-n, C-y, O-n, O-y
O-n
Pr2
Fnd1
Fans delay after defrost, section 1
0÷255 min.
10
Pr2
FSt1
Fans stop temperature, section 1
-50,0÷110°C/ -58÷230°F
2.0
Pr2
FAP1
Probe for fans
P1÷P3
P2
Pr2
FnC2
Fans operating mode, section 2
C-n, C-y, O-n, O-y
O-n
Pr2
Fnd2
Fans delay after defrost, section 2
0÷255 min.
0
Pr2