background image

dIXEL

dIXEL

dIXEL

dIXEL

    

Operating manual 

cod. 1592

cod. 1592

cod. 1592

cod. 1592017

017

017

017050

050

050

050    

 

1592017050  XLR470 GB r1.0 24.05.07.doc 

XLR470 

3/18 

1.

 

GENERAL WARNINGS 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding  sudden  temperature  changes  with  high 
atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see address) with a detailed description of 
the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XLR470

, 32x74 mm format, is a microprocessor based controller, able to control 2 temperatures in an independent way.  

The  first  section

  is  suitable  for  applications  on  medium  or  low  temperature  refrigerating  units.  It  is  provided  with  3  relay  outputs  to  control 

compressor, defrost - which can be either electrical or hot gas  - and the evaporator fans. It is also provided with 2 NTC or PTC probe inputs, one for 
temperature control the other one to control the defrost end temperature of the evaporator.  

The  second  section

  is  suitable  for  applications  on  medium  or  low  temperature  refrigerating  units.  It  is  provided  with  3  relay  outputs  to  control 

compressor, defrost - which can be either electrical or hot gas  - and the evaporator fans. It is also provided with 2 NTC or PTC probe inputs, one for 
temperature control the other one to control the defrost end temperature of the evaporator.. 
There are two digital inputs (free contact) completely configurable by parameters. 
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a 

ModBUS-RTU 

compatible monitoring system and 

to programme the parameter list with the 

“Hot Key”.

 

 

3.

 

TEMPERATURE CONTROL 

1.

 

THE COMPRESSOR 1 (2) 

 

For  each  section,  the  regulation  is  performed  according  to  the 
temperature measured by its own thermostat probe with a positive 
differential from the set point. 
If  the  temperature  increases  and  reaches  set  point1  (2)    plus 
differential1 (2) the compressor is started and then turned off when 
the temperature reaches the set point value again. 

In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters “

COn1(2)

” and “

COF1(2)

”. 

4.

 

DEFROST 

1.

 

SECTION 1 

For the 

section 1

 two defrost modes are available through the “

tdF1

” parameter:  

tdF1= rE 

defrost with electrical heater  

tdF1= in

 or hot gas.  

The defrost interval is control by means of parameter “

EdF1

”: 

rtc (only for instruments with RTC): 

beginning of defrost cycles is set by the 

L1d1÷L1d6

 parameters during the working days and 

S1d1÷S1d6

 

during the holidays  

in

 the defrost is made every “

IdF1

” time 

Sd

 the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON) 

At the end of defrost the drip time is controlled through the “

Fdt1

” parameter. 

 

Содержание COOL MATE XLR470

Страница 1: ...al cod 1592 cod 1592 cod 1592 cod 1592017 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 1 18 Dual temperature controller XLR470 XLR470 XLR470 XLR470 C C C COOL OOL OOL OOL M...

Страница 2: ...________ 5 7 DISPLAY ____________________________________________________________________ 5 8 PARAMETER LIST ____________________________________________________________ 7 9 DIGITAL INPUTS ___________...

Страница 3: ...frost which can be either electrical or hot gas and the evaporator fans It is also provided with 2 NTC or PTC probe inputs one for temperature control the other one to control the defrost end temperat...

Страница 4: ...The defrost of the 2 sections of controller starts at the same time idF1 parameter sets the defrost interval for both the sections The defrosts are performed at regular interval if EdF1 in or accordin...

Страница 5: ...fans will run continuously also during defrost An additional parameter FSt2 provides the setting of temperature detected by the evaporator probe 2 above which the fans are always OFF This can be used...

Страница 6: ...n within 15s To memorise the new set point value push the SET1 or SET2 key again or wait 15s 1 6 HOW TO START A MANUAL DEFROST FOR THE SECTION 1 OR SECTION 2 To start a defrost for the section 1 push...

Страница 7: ...ntial1 0 1 25 5 C 1 45 F Intervention differential for set point1 always positive Compressor1 Cut IN is Set Point Plus Differential1 Hy1 Compressor1 Cut OUT is when the temperature reaches the set poi...

Страница 8: ...1 0 60 min time interval between reaching defrost termination temperature and the restoring of the control s normal operation This time allows the evaporator to eliminate water drops that might have...

Страница 9: ...h ALc2 Ab absolute value minimum alarm is enabled when the probe values goes below the ALL2 value ALd2 Temperature alarm delay section 2 0 255 min time interval between the detection of an alarm condi...

Страница 10: ...C 54 54 F sets the increasing value of the set point2 during the Energy Saving cycle TO SET CURRENT TIME AND WEEKLY HOLIDAYS ONLY WITH RTC Hur Current hour 0 23 h Min Current minute 0 59min dAY Curren...

Страница 11: ...section 2 bAL serious alarm it counts for both the sections As soon as the digital input is activated the unit will wait for did1 time for section 1 and did2 time for section 2 delay before signallin...

Страница 12: ...7 017 017 017050 050 050 050 1592017050 XLR470 GB r1 0 24 05 07 doc XLR470 12 18 87 230 M A X 3 7 210 130 120 M AX 2 8 H I FIG 3 A Fig 6 200 61 0 0 172 106 44 190 18 Fig 4 200 192 5 185 61 12 6 0 0 4...

Страница 13: ...entres signed in the bottom cover of the Cool Mate Fig 3 H I 6 Fix the cablepresses and the pipepresses 7 Insert the wiring cables in cablepresses or in the pipepresses 8 Join the back and frontal par...

Страница 14: ...e memory problems Alarm output ON Other outputs OFF dA Door switch alarm Outputs unchanged EAL External alarm Outputs unchanged bAL Serious external alarm Regulation outputs deactivated rtc RTC data w...

Страница 15: ...ac defrost1 relay SPDT 16 3 A 250Vac defrost2 relay SPST 5 A 250Vac fan1 relay SPST 5 A 250Vac fan2 relay SPST 5 A 250Vac light relay SPDT 16 A 250Vac alarm relay SPST 8 3 A 250Vac Other output Direct...

Страница 16: ...alization P1 P4 P1 Pr2 Lod2 Upper display visualization P1 P4 P3 Pr2 DEFROST dFS Relation between defrosts ind StS Sti SE ind Pr2 tdF1 Kind of defrost section 1 rE in rE Pr2 EdF1 Defrost mode section...

Страница 17: ...3P Thermostat 2 probe presence n y Y Pr2 P4P Evaporator 2 probe presence n y Y Pr2 DIGITAL INPUTS I1P Digital input 1 polarity cL OP cL Pr2 i1F Digital input 1 operating mode MP1 MP2 MP EA1 EA2 EAL bA...

Страница 18: ...0 23h 50 min nu 6 0 Pr2 L2d2 2nd workdays defrost start Section 2 0 23h 50 min nu 13 0 Pr2 L2d3 3rd workdays defrost start Section 2 0 23h 50 min nu 21 0 Pr2 L2d4 4th workdays defrost start Section 2...

Отзывы: