background image

B

C

2.

A12 / LMC-1 / E

-CD

Damper actuators LMC...

(with fast running time)

Spindle clamp versions

Actuators for for heating, 
ventilation, air-conditioning

new

supplement to

replaces several data sheets

OEM

at004707

at001707

at021901

KARTY KATALOGOWE

j. polskim

przesyłamy na życzenie 

fax-em!!!

Biuro Handlowe

MERPRO Sp. z o.o.

ul. Ścinawska 43

60-178 POZNAŃ
tel. 0048  61 8685629  
fax 0048  61 8685940
E-mail: [email protected]
www.merpro.pl

Содержание LMC230

Страница 1: ...heating ventilation air conditioning new supplement to replaces several data sheets OEM at004707 at001707 at021901 KARTY KATALOGOWE w j polskim przesyłamy na życzenie fax em Biuro Handlowe MERPRO Sp z o o ul Ścinawska 43 60 178 POZNAŃ tel 0048 61 8685629 fax 0048 61 8685940 E mail bh merpro pl www merpro pl ...

Страница 2: ...d for the operation of air dampers in HVAC systems Torque requirements When calculating the torque required to operate dampers it is essential to take into account all the data supplied by the damper manufacturer concerning cross sectional area design mount ing and air flow conditions B C ...

Страница 3: ...trol and monitoring functions 10 Contents Nominal voltage AC 24 V DC 24 V AC 230 V Running time 25 35 s Control Open Close Single wire 2 wire Modulating DC 0 10 V Direction of rotation reversible right left Manual operation by pushbutton Auxiliary switch potential free Mechanical angle of rotation limiting Electronic angle of rotation limiting Continuous position feedback Damper rotation with univ...

Страница 4: ... time 35 s Dimensions Subject to technical changes 01 00 Direction of rotation selected with L R switch Torque min 2 Nm at rated voltage Angle of rotation max 95 adjustable by mechanical stops Running time 25 35 s 0 2 Nm Power consumption 2 W For wiring sizing 3 VA Nominal voltage AC 24 V 50 60 Hz DC 24 V Nominal voltage range AC DC 19 2 28 8 V Manual operation pushbutton self resetting Auxiliary ...

Страница 5: ...stops Flexible signalling 0 100 with adjust able auxiliary switch LMC230 S only Mounting instructions page 6 Adjusting auxiliary switch LMC230 S page 7 Important Read the notes about the use and torque requirements of the damper actuators on page 2 Dampers up to approx 0 4 m2 Open Close actuator AC 230 V Control by single pole contact single wire control Running time 35 s Direction of rotation sel...

Страница 6: ...Mounting instructions LMC24 S LMC230 S 6 3 2 1 m i n 3 5 m m 6 16 3 5 6Nm 1mm 2 1 1 3 2 5 4 m0001707 Subject to technical changes 01 00 B C ...

Страница 7: ...switch is needed to operate e g at 60 angle of rotation Turn the scale knob of the auxiliary switch anticlockwise ccw until the tip of the arrow is just past the scale zero Connection S1 to S3 made and switching position set for 60 angle of rotation Option 2 Actuator at switching position Procedure Depress the manual operation pushbutton and move the actuator to the position where the auxiliary sw...

Страница 8: ...ee of protection IP 54 bottom cable entry Ambient temperature range 30 50 C Non operating temperature 40 80 C Humidity test to EN 60335 1 EMC CE according to 89 336 EEC 92 31 EEC 93 68 EEC Maintenance maintenance free Weight 620 g Dampers up to approx 0 4 m2 Modulating damper actuator AC DC 24 V Control DC 0 10 V and posi tion feedback DC 2 10 V Running time 35 s Application The type LMC24 SR is i...

Страница 9: ... 2 1 1 2 3 4 5 Mounting instructions for LMC24 SR 9 Mounting on anticlockwise closing damper Mounting on clockwise closing damper m i n 3 5 m m 6 16 3 2 1 3 5 6Nm 2 1 100 20 1 2 3 4 5 m0006707 m0007707 Subject to technical changes 01 00 B C ...

Страница 10: ...umption data Y DC 0 10 V a b 5 U a b control mode T Reversing switch R Reversing switch L T AC 24 V DC 24 V Connect via safety isolating transformer Y 1 2 3 Position indication LMC24 SR 5 U T AC 24 V T 1 2 3 ZAD24 4 Direction of rotation Connect via safety isolating transformer Y 1 2 3 Master slave control depending on position LMC24 SR 5 1 2 3 5 to next actuator Master actuator Note 5 synchronism...

Отзывы: