7.10 PROPORTIONAL OUTPUTS CONFIGURED FOR PILOTING AN EXTERNAL RELAY
GND = common
It is possible to connect a relay with a 12 volt coil in continuous current with maximum absorption of 40 mA.
7.11 VGIPC REMOTE TERMINAL COLLECTION
It is possible to connect up to two remote terminals in parallel, each with an NTC probe on board. If the
remote terminal with NTC probe is used, the display of the controlled temperature and/or temperature control
can be given by the probe on the terminal. The remote terminals can be “interfaced” directly using a
SHIELDED
cable up to 150M.
WARNING:
If the power supply polarity is not respected, the remote terminal and the iPro.CHILL
programmable controller can be damaged irreparably