USER MANUAL – Release 1.2 of 01/01/2010
Page 182 of 191
Version: 02/03/2010
57.35
RTC ALARM
Display label meaning
ArtC
(clock alarm)
Cause of activation
Clock to be regulated
Reset
Regulated clock
Reset
Manual. (reset procedure in functions menu)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Loads
They follow their regulation
Energy saving function
Deactivated
Automatic on/off function
Deactivated
57.36
RTF ALARM
Display label meaning
ArtF
(clock alarm)
Cause of activation
Clock breakdown
Reset
Clock replacement
Reset
Manual. (reset procedure in functions menu)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Loads
They follow their regulation
Energy saving function
Deactivated if in time span function
Automatic
switch-on/off
function
deactivated
57.37
EEPROM ALARM
Display label meaning
AEE
Cause of activation
Eeprom failed
Reset
-------
Reset
Manual
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Loads
Off