!
USER MANUAL – Release 1.2 of 01/01/2010
Page 26 of 191
Version: 02/03/2010
Unit
CF 1
Defines the type of unit to control
0 = Air to air unit
1 = Air to water
2 = Water to water
0
2
CF 2
Selection of unit working mode
1 = cooling only
2 = heating only
3 = cooling and heating
0
3
CF 3
Selection of compressors enabling
0 = cooling and heating
1 = cooling only
2 = heating only
0
2
CF 4
Condensing unit
0 = no
1 = yes
With CF04 = 1 the heating temperature control, the dynamic set point and the
energy saving functions are automatically disabled
0
1
Compressors
CF 5
Number of circuit n° 1 compressors (at least 1 compressor in circuit 1 must be
configured)
1 = 1
2 = 2
3 = 3
4 = 4
1
4
CF 6
Number of compressors in circuit n° 2
0 = 0
1 = 1
2 = 2
3 = 3
4 = 4
0
4
CF 7
Number of compressors in circuit n° 3
0
4
CF 8
Number of compressors in circuit n° 4
0
4
CF 9
Number of unloaders in circuit 1 compressors
0 = none
1 = 1
2 = 2
3 = 3
0
3
CF 10
Number of unloaders in circuit 2 compressors
0
3
CF 11
Number of unloaders in circuit 3 compressors
0
3
CF 12
Number of unloaders in circuit 4 compressors
0
3
Unit Set Up
Parameter Description
min
max
udm
Resolution
Analogue Inputs
SP 1
Temperature or pressure analogue input working:
0 = Temperature / pressure NTC – 4÷20 mA:
The condensing temperature is controlled by the NTC probe
The control of the circuits evaporating pressure and of the pressure probe
configured as auxiliary output is made by the 4÷20mA input
1 = Pressure control with
4÷20 mA input:
The evaporating and condensing pressures control is made by a 4÷20mA
transducer.
2 =
Temperature / pressure
NTC – 0÷5V:
The condensing temperature is controlled by the NTC probe
The control of the circuits evaporating pressure and of the pressure probe
configured as auxiliary output is made by the 0÷5V input
3 =
Pressure control with 0÷5V input:
The evaporating and condensing pressures control is made by a 0÷5V
transducer.
0
3
Remote terminal
Parameter Description
min
max
udm
Resolution
SP 2
Remote terminal configuration n° 1
0= not present
1= NTC probe on board
2= without NTC probe on board
0
2
SP 3
Remote terminal configuration n° 2
0= not present
1= NTC probe on board
2= without NTC probe on board
0
2