!
USER MANUAL – Release 1.2 of 01/01/2010
Page 173 of 191
Version: 02/03/2010
57.23
HEAT RECOVERY DISABLING SIGNAL DUE TO HIGH CONDENSATION
TEMPERATURE/PRESSURE IN COOLING WORKING MODE
Display label meaning
b1rC
(circuit n° 1 recovery disabling signal)
b2rC
(circuit n° 2 recovery disabling signal)
b3rC
(circuit n° 3 recovery disabling signal)
b4rC
(circuit n° 4 recovery disabling signal)
Cause of activation
When working, if the probe configured as condensation temperature or
pressure control measures a value > rC06 set
Reset
!
of the condensation pressure or temperature measures a value < rc05 set
– rC07 differential
!
By heat recovery disabling function inserted after the Par. rC08 time set
Reset
Automatic
Icon
flashing
Action
Alarm relay + buzzer NOT activated
Regulators
Alarm
Relay + buzzer NOT activated
Reverse valve
It follows its regulation
Recovery valve
Off
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
It follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
It follows its regulation
Condensation ventilation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressors
It follows its regulation
Pump down solenoid valve It follows its regulation