5–28
SF3x Storage Enclosure FRU Replacement
5.7 Cable Replacement Procedures
NOTE
Do
not
disconnect any DSSI interconnect cables while power is
applied to the storage array (all installed ISEs) and the system(s).
The ac power cord, power harness, OCP cables, and DSSI cables are
storage enclosure FRUs.
The OCP cables run down the side of the inner assembly from the
transition module to the front and rear backplanes.
The DSSI interconnect cables run from the rear bulkhead, over the top of
the inner assembly to the front and rear backplanes. You must replace all
the cables for a port when replacing a single cable.
The removal and replacement procedures for these FRUs are as follows:
• AC power cord, (Section 5.7.1)
• OCP to TM cable, (Section 5.7.2)
• Power harness, (Section 5.7.3)
• Internal DSSI cables, (Section 5.7.4)
Содержание EK-SFXXS-SG-003
Страница 1: ...DECarray Service Guide EK SFXXS SG 003 Digital Equipment Corporation ...
Страница 10: ......
Страница 18: ...1 8 Introduction Figure 1 3 SF7x Series Storage Enclosure SHR_X1123C_89 ...
Страница 24: ......
Страница 44: ......
Страница 56: ......
Страница 59: ...DECarray FRU Removal and Replacement 4 3 Figure 4 1 Removing DECarray Door DOOR HINGE S H R X 0 0 1 2 9 1 ...
Страница 168: ...6 60 SF7x Storage Enclosure FRU Replacement Figure 6 18 Enclosure Internal DSSI Cables ...
Страница 169: ...SF7x Storage Enclosure FRU Replacement 6 61 Figure 6 19 Enclosure Internal DSSI Cables cont ...
Страница 170: ...6 62 SF7x Storage Enclosure FRU Replacement Figure 6 20 Enclosure Internal DSSI Cables cont ...
Страница 176: ......
Страница 180: ......
Страница 220: ......
Страница 224: ......