SF3x Storage Enclosure FRU Replacement
5–7
Example 5–2
SHOW CLUSTER
$ SHOW CLUSTER
View of Cluster from system ID 63973
node: CLOUDF
+-------------------+---------+
|
SYSTEMS
| MEMBERS |
+--------+----------+---------+
|
NODE
| SOFTWARE |
STATUS |
+--------+----------+---------+
| CLOUDF | VMS V5.4 | MEMBER
|
| R2CYAA | RFX V200 |
|
| R2RRBA | RFX V200 |
|
+--------+----------+---------+
NOTE
Record the node names (in this example, R2CYAA and
R2RRBA) for use later in this procedure.
2. Establish a connection to the suspected disk ISE by using the SET
HOST/DUP command. This step requires a privileged account. If
you cannot establish a connection due to the nature of the disk ISE
problem, then use the alternate method outlined in the next step to
determine disk ISE parameters.
Display and record the disk ISE parameters as shown in Example 5–3.
In this case, the parameter values are:
NODENAME
R2CYAA
SYSTEMID
404194100302
ALLCLASS
1
FIVEDIME
1
UNITNUM
21
FORCEUNI
0
Содержание EK-SFXXS-SG-003
Страница 1: ...DECarray Service Guide EK SFXXS SG 003 Digital Equipment Corporation ...
Страница 10: ......
Страница 18: ...1 8 Introduction Figure 1 3 SF7x Series Storage Enclosure SHR_X1123C_89 ...
Страница 24: ......
Страница 44: ......
Страница 56: ......
Страница 59: ...DECarray FRU Removal and Replacement 4 3 Figure 4 1 Removing DECarray Door DOOR HINGE S H R X 0 0 1 2 9 1 ...
Страница 168: ...6 60 SF7x Storage Enclosure FRU Replacement Figure 6 18 Enclosure Internal DSSI Cables ...
Страница 169: ...SF7x Storage Enclosure FRU Replacement 6 61 Figure 6 19 Enclosure Internal DSSI Cables cont ...
Страница 170: ...6 62 SF7x Storage Enclosure FRU Replacement Figure 6 20 Enclosure Internal DSSI Cables cont ...
Страница 176: ......
Страница 180: ......
Страница 220: ......
Страница 224: ......