SF7x Storage Enclosure FRU Replacement
6–25
This message indicates that DRVTST executed successfully.
If an error condition is found during the execution of DRVTST, an error
message is displayed. Two types of errors are reported:
• Soft errors, which are corrected during the operation of the disk ISE
• Fatal errors, which prevent the disk ISE from functioning
Table 6–2 indicates the error messages you may see and what they mean.
Table 6–2
DRVTST Error Messages
Message
Description
Soft read error on head xx track yyyy.
Soft write error on head xx track yyyy.
Soft compare error on head xx track
yyyy.
These are soft error messages indicating that
an operation succeeded, but that the error
recovery firmware was invoked. These messages
may indicate a forced-error flag or correctable
ECC error, or that the read/write head was
temporarily off-track. These soft errors are
corrected during normal operation.
xxxx - Unit diagnostics failed.
This is a fatal error. The xxxx is the MSCP error
code.
xxxx - Unit read/write test failed.
This is a fatal error. The xxxx is the MSCP error
code.
6.1.3.5 Mounting the Disk ISE
Once testing completes successfully, you can mount the disk ISE. Again, if
you replaced the HDA, restore data with BACKUP.
The SHOW CLUSTER command will continue to show the original name
of the replacement drive module. This ‘‘ghost’’ will not harm anything and
will disappear only after the next reboot.
NOTE
A moderate increase in error counts is to be expected after this
warm swap procedure has been correctly completed.
Содержание EK-SFXXS-SG-003
Страница 1: ...DECarray Service Guide EK SFXXS SG 003 Digital Equipment Corporation ...
Страница 10: ......
Страница 18: ...1 8 Introduction Figure 1 3 SF7x Series Storage Enclosure SHR_X1123C_89 ...
Страница 24: ......
Страница 44: ......
Страница 56: ......
Страница 59: ...DECarray FRU Removal and Replacement 4 3 Figure 4 1 Removing DECarray Door DOOR HINGE S H R X 0 0 1 2 9 1 ...
Страница 168: ...6 60 SF7x Storage Enclosure FRU Replacement Figure 6 18 Enclosure Internal DSSI Cables ...
Страница 169: ...SF7x Storage Enclosure FRU Replacement 6 61 Figure 6 19 Enclosure Internal DSSI Cables cont ...
Страница 170: ...6 62 SF7x Storage Enclosure FRU Replacement Figure 6 20 Enclosure Internal DSSI Cables cont ...
Страница 176: ......
Страница 180: ......
Страница 220: ......
Страница 224: ......