5–38
SF3x Storage Enclosure FRU Replacement
18. If necessary, tape the two DSSI cables for that side of the enclosure
together.
19. Replace the fan assembly.
WARNING—USE TWO PEOPLE.
Use two people to place the inner assembly back into the
extrusion tube mounted in the storage array.
20. Slide the inner assembly back into the extrusion tube. Secure the
front panel captive screws. Do not use excessive force as it may strip
the threads in the extrusion tube.
21. Replace the four screws at each corner of the enclosure frame.
22. Replace the OCP by aligning the OCP connector pins with the TM clip
fasteners on the transition-termination module. Push, do not force,
the OCP into the fasteners by applying equal pressure to both sides.
23. At the rear of the storage enclosure, reconnect the ac power cord to
the ac receptacle on the power supply.
24. Replace the DSSI interconnect cables to the rear bulkhead of the
enclosure.
25. Restore the enclosure to service, and run the checkout procedure
found in Section 5.9.
Содержание EK-SFXXS-SG-003
Страница 1: ...DECarray Service Guide EK SFXXS SG 003 Digital Equipment Corporation ...
Страница 10: ......
Страница 18: ...1 8 Introduction Figure 1 3 SF7x Series Storage Enclosure SHR_X1123C_89 ...
Страница 24: ......
Страница 44: ......
Страница 56: ......
Страница 59: ...DECarray FRU Removal and Replacement 4 3 Figure 4 1 Removing DECarray Door DOOR HINGE S H R X 0 0 1 2 9 1 ...
Страница 168: ...6 60 SF7x Storage Enclosure FRU Replacement Figure 6 18 Enclosure Internal DSSI Cables ...
Страница 169: ...SF7x Storage Enclosure FRU Replacement 6 61 Figure 6 19 Enclosure Internal DSSI Cables cont ...
Страница 170: ...6 62 SF7x Storage Enclosure FRU Replacement Figure 6 20 Enclosure Internal DSSI Cables cont ...
Страница 176: ......
Страница 180: ......
Страница 220: ......
Страница 224: ......