This state indicates that Zones 1 and 2 have entered the alarm setting, or the trigger
manual pushbutton has been activated. In this state the central carries out the following
actions:
•
Activated Mode indicator (second state).
•
Increase the output frecuency of the sounder output State 1:
2 Hz.
•
Sirens’ ON indicator State 2.
•
Sirens’ output activation State 2:
continuous tone.
•
Acoustic indicator:
continuously.
•
Display activation:
Shows the countdown until the triggering of the extinction,
(Display shows it intermittently).
This state can’t silence the state sirens, neither canceling the extinction block if the
process can be reseted( EN12094-1 requirement).
Once the activate mode is reached, the following actions can be carried out:
•
Activation of the manual external Pause push buttons:
For the Extinction process
meanwhile they’re pushed.
•
Activation of the manual external Stop push buttons:
Stops definitely the
extinction process.
6.6.4- Extinción Estado Disparado
This state indicates that the countdown initiated in the previous state has reached 0.
( This state could not be reached in case of fault in any of the stop or cancel manual
push buttons). In this state the following actions are carried out:
•
Acoustic indicator:
Continously sounding.
•
Triggered State indicator:
blinking
•
Activation output sounder state 1:
4Hz
•
Activation output sounder state 2: continuous tone.
•
Activation of the sing
“Do not enter, extinction triggered”.
•
On indicator of sign and bottle:
Fixed
•
Activation of the bottle exit :
Activation of the bottles’ solenoid.
•
Acoustic indicator active:
continuously.
•
Displays’ activation:
Shows 000 intermittently.
•
•
•
6.6.5- Triggering Ended Extinction State
Once the previous state is reached and the inundation time is over (progammable
timer, 60 seconds fabric setup).
The extinction process is finished.
Содержание CCD-103
Страница 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Страница 2: ......
Страница 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Страница 4: ......
Страница 6: ......
Страница 14: ...12 ES 4 Guía de conexionado de la PCB ...
Страница 44: ......
Страница 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Страница 46: ......
Страница 48: ......
Страница 56: ...12 GB 4 PCB connection guide ...
Страница 86: ......
Страница 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Страница 88: ......
Страница 90: ......
Страница 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Страница 128: ......
Страница 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Страница 130: ......
Страница 132: ......
Страница 140: ...12 IT 4 Guía de conexionado de la PCB ...
Страница 170: ...55310300 2014 10 14 ...