28
GB
6.4.3- Fault mode
The unit is in fault mode when there is a fault in the unit. The fault is indicated as
follows:
•
General fault Led active:
Activated intermittently.
•
Fault LED active:
Activated intermittently depending on the type of fault: zone fault,
power supply fault, sounders fault.
•
Acoustic warning active:
Intermittently.
•
Fault output active .
Actions in case of fault:
Once it is in fault mode, you can do the following:
•
Press the station silence key:
Silences the buzzer and activates the buzzer silenced
warning.
•
Press the reset key:
The unit will return to standby.
Section 9 lists the most common fault and how to repair them.
6.4.4- Disable mode
The panels in the conventional range allow zones and sounders to be disconnected.
When a zone is disconnected, the panel does not show any incident or event in the
disconnected zone, therefore it is important to limit the use of this operation.
The disconnection state warnings are the following:
•
Cancel warning:
Active continuously.
•
Zone cancelled warning:
Led up continuously indicating the specific zone that has
been cancelled.
•
Sounders cancelled warning:
Led up continuously indicating the sounders have
been cancelled.
Connecting/disconnecting zones:
To connect and disconnect an area, press the zone key:
•
With the zone connected, press the zone key twice — Zone disconnect.
•
With the zone disconnected, press the zone key Zone connect.
If the delay time is running, this will be cancelled and the sirens will remain inactive.
Note: The keys must be pressed with the key in the ON position.
Содержание CCD-103
Страница 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Страница 2: ......
Страница 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Страница 4: ......
Страница 6: ......
Страница 14: ...12 ES 4 Guía de conexionado de la PCB ...
Страница 44: ......
Страница 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Страница 46: ......
Страница 48: ......
Страница 56: ...12 GB 4 PCB connection guide ...
Страница 86: ......
Страница 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Страница 88: ......
Страница 90: ......
Страница 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Страница 128: ......
Страница 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Страница 130: ......
Страница 132: ......
Страница 140: ...12 IT 4 Guía de conexionado de la PCB ...
Страница 170: ...55310300 2014 10 14 ...