GB
13
The extinguishing panel connections are divided into two blocks.
Conventional detection block, with the following inputs and outputs:
- Zone Inputs 1,2 and 3.
- Alarm and Fault relay outputs.
- General alarm sounder output.
- 24 V aux. output.
- Exterior input.
- Ventilation relay output.
Extinction block, with the following inputs and outputs:
- Extinction bottle solenoid output.
- Warning sign “Don’t enter extinction active” output.
- State 1 and 2 sounder outputs.
- Triggering, stop and hold MCP inputs.
- Door surveillance and 2 bottle surveillance inputs.
.
As indicated in the drawing above, the positive connects to contact number 1 both in
the input and output. The negative connects to the line input at contact 4 and leaves
through contact 3 to the following detector. At the end of the line you must place a
4K7 end-of-line. Remember that the maximum number of detectors per zone is 32
detectors or 32 MCP.
If you are not going to use all the zones, it is necessary to connect the end-of-line
resistor (4.7kOhm) at the terminals of the not used zone in order to avoid a fault signal
from the system.
4.1- Detection Block Connection
4.1.1- Detectors Connection
In the factory default configuration, the extinguishing panel has 3 zones. Zones 1 and
2 work as crossed zones in order to activate the automatic extinction process. Zone 3
is an independent zone for adjacent zones.
The extinguishant fire panel is compatible with the conventional range detectors and it
will not work properly with another detectors
Содержание CCD-103
Страница 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Страница 2: ......
Страница 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Страница 4: ......
Страница 6: ......
Страница 14: ...12 ES 4 Guía de conexionado de la PCB ...
Страница 44: ......
Страница 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Страница 46: ......
Страница 48: ......
Страница 56: ...12 GB 4 PCB connection guide ...
Страница 86: ......
Страница 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Страница 88: ......
Страница 90: ......
Страница 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Страница 128: ......
Страница 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Страница 130: ......
Страница 132: ......
Страница 140: ...12 IT 4 Guía de conexionado de la PCB ...
Страница 170: ...55310300 2014 10 14 ...