3.3.5- Electrical wiring
It is recommended that the equipment is powered and tested before connecting
devices such as sensors, manual call points etc.
The panel must be connected via an external circuit breaker using a 1.5 mm2 cable
section. The voltage should be 230V.
To avoid crossing the network, the mains cable must be separated from the zones
cables.
If the system can be affected by an electrical disturbance, we recommend the use of a
ferrite tube as close as possible to the connection.
It is imperative to use the holes marked in the box for connecting the power supply
wires and those from the areas to the terminal block. Use a “crown” drill bit to
perforate the box and insert the PG13 type gland. For introducing the mains cable, it is
recommended to use the input placed in the back part of the mains block.
It is recommended to use shielded cable: Conect the shielded cable to the cable
passages and ensure the instalation has a correct ground connection.
Содержание CCD-103
Страница 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Страница 2: ......
Страница 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Страница 4: ......
Страница 6: ......
Страница 14: ...12 ES 4 Guía de conexionado de la PCB ...
Страница 44: ......
Страница 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Страница 46: ......
Страница 48: ......
Страница 56: ...12 GB 4 PCB connection guide ...
Страница 86: ......
Страница 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Страница 88: ......
Страница 90: ......
Страница 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Страница 128: ......
Страница 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Страница 130: ......
Страница 132: ......
Страница 140: ...12 IT 4 Guía de conexionado de la PCB ...
Страница 170: ...55310300 2014 10 14 ...