38
GB
9- Common problems:
PROBLEM
SINTOMA
ACTION
POWER SUPPLY
There is no power
supply
The panel’s service LED is not lit up
•
Check the mains (230V)
•
Check the mains fuse.
•
Check the battery.
•
Check the battery fuse.
POWER SUPPLY
Fault in a fuse
The panel has the general fault and
power supply failure lights lit and the
buzzer sounds intermittently.
•
Check the mains (230)
•
Check the mains fuse.
•
Check the battery connection.
•
Check the battery fuse.
•
Check the voltage of the batte
-
ries (Vbat>24 V)
•
Check the voltage of the bat
-
tery charger 27,6 V
POWER SUPPLY
Out of service
The panel has the general fault
and out of service lights lit and the
buzzer sounds intermittently.
•
Disconnect the battery until
you can re-establish the mains
supply or some charged batte-
ries.
ZONES
Faut in zone
The panel has the general fault and
zone failure lights lit and the buzzes
sounds intermittently.
•
Check the sounders (4K7)
•
Check that there are no short
circuits or cuts in the sounders
output line
•
Check that no sounders are
inverted.
SURVEILLANCE
OUTPUTS
Sounder output fault,
bottle, sign, state 1
SND, state 2 SND
The general fault indicator is
blinking and also the indicator of
one of the nexts outputs is blinking:
Sounder outputs, Bottle, Sign, State
1 SND, state 2 SND. The buzzer is
intermittently sounding.
•
Check the end-of-line resistor
of the zone (4K7).
•
Check there are no short cir
-
cuits or cuts in the zone line.
•
Check there are no elements
with inverted polarity.
SURVEILLANCE
INPUTS OF THE EX
-
TINCTION BLOCK
Fault in any of the
MCP inputs, door,
bootle surveillance.
The general fault indicator is blin-
king and also the indicator of one of
the nexts outputs is blinking:MCP,
Door, bottle surveillance. The buzzer
is intermittently sounding.
•
Check the end-of-line resistor
of the zone (4K7).
•
Check there are no short cir
-
cuits or cuts in the zone line.
•
Check that no buttons are
activated without resistance.
Содержание CCD-103
Страница 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Страница 2: ......
Страница 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Страница 4: ......
Страница 6: ......
Страница 14: ...12 ES 4 Guía de conexionado de la PCB ...
Страница 44: ......
Страница 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Страница 46: ......
Страница 48: ......
Страница 56: ...12 GB 4 PCB connection guide ...
Страница 86: ......
Страница 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Страница 88: ......
Страница 90: ......
Страница 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Страница 128: ......
Страница 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Страница 130: ......
Страница 132: ......
Страница 140: ...12 IT 4 Guía de conexionado de la PCB ...
Страница 170: ...55310300 2014 10 14 ...