![Desin Instruments HS-7000 Series Скачать руководство пользователя страница 96](http://html1.mh-extra.com/html/desin-instruments/hs-7000-series/hs-7000-series_general-instructions-manual_2486942096.webp)
96
CONTROL SETPOINT SP
CONFIGURATION OF MAIN PARAMETERS OF SP 1, SP 2 AND SP 3:
●
Number of decimals:
- In
[ConF] [SP 1..2..3]
in parameter
[P 02]
modify the digit “n” in
[?n??]
.
- Set
[P 02]
[?n??]
to
0
(no decimals),
1
(000.0),
2
(00.00),
3
(0.000) according to the
decimals required.
Note:
This parameter should have the same number of decimals as its input signal.
●
Remote Setpoint Assignment:
The Local Setpoint SP value can be set by the front panel keypad.
However, in some cases it would be necessary to shift from local setpoint to remote setpoint
coming from local internal variable or remote one.
- In
[ConF] [SP 1..2..3]
in parameter
[P 01]
check
[??nn]
- Configured as Remote SP, the parameter
[P 01]
should have the code
[??11]
corresponding
to the signal of Analog Input AI 3 or S
- When not used, the parameter
[P 01]
has the code
[??04]
corresponding to input without
signal.
- Configured as Remote SP different from AI 3, the parameter
[P 01]
can be set to:
Arithmetic operator value “Art 1”...”Art 4”
[??30]
or
[??31]
or
[??32]
or
[??33]
Señal procedente de las Constantes Str 1..2..3..4
[??15]
or
[??16]
or
[??17]
or
[??18]
User Linearization value Lin 1 or Lin 2
[??28]
or
[??29]
Derivator value Der 1 or Der 2
[??25]
or
[??26]
Signal selected by one of the selectors Sel 1, Sel 2, Sel 3
[??19]
or
[??20]
or
[??21]
●
Setpoint SP Limits Setting
Define the Hi and Lo limits of the Setpoint SP.
The introduced setpoint SP value, local or remotely, will be limited to the Lo and Hi limits set
previously.
Limits selectable between -32000 and 32000.
Low Setpoint SP Limit.
Factory setting by default to
0
- In
[ConF] [SP 1..2..3]
in parameter
[P 04]
introduce the required low limit value in
[nn]
[nnnn]
without decimals.
High Setpoint SP Limit.
Factory setting by default to
10000
- In
[ConF] [SP 1..2..3]
in parameter
[P 05]
introduce the required high limit value in
[nn]
[nnnn]
without decimals.