ALARM CONFIGURATION [AL 1...6]
The selection of the alarm type Deviation or Independent, High or Low, of each of the Alarms
[AL 1], [AL 2], [AL 3], [AL 4], [AL 5]
and
[AL 6]
, as well as, the assignment of the input or
output, can be realized by the configuration of the correspondent option in
[Menu]
[ConF]
. See
Configuration by Keypad.
MODIFICATION OF ALARM SETPOINTS [SPA 1...6]
In the HS-7300 Series the maximum limit is --1999 to 9999 points while in the HS-7200 and
HS-7500 is ± 32000 points, however, can be limited to any value in-between.
The number of decimals 0, 1, 2 or 3, can be configured by keypad or by LoopWin software. See
Advanced Programming.
Each one of the alarm Setpoints
SPA 1...6
, can be located, by programming, in any of the used
loops, as well as, can be protected by Password level. See Advanced Programming.
- Select by
key one of the
L1, L2 or L3
indicated by the correspondent LED, where the alarm
to modify is located.
AL 1 and AL 2
in Loop 1,
AL 3 and AL 4
in Loop 2,
AL 5 and AL 6
(in
Loop 3).
- Once the loop to modify is selected, press key
until the alarm to modify is displayed (
AL
1
to
AL 6
).
- Press
to go in the alarm. The display shows
[xxxx]
[SPA n]
where “n” is the alarm number
and [xxxx] is the actual setpoint value of this alarm.
- Press
again in order to modify. The unity digit start flickering.
- Press to change the value of the digit and then press
to shift to the next digit repeating
the process until achieving the new alarm value.
- Press
to save the new value, or press
to modify the hysterisis
[0001]
[Hi n]
.
- To exit press
repeatedly, until
NORMAL DISPLAY.
NOTE 1:
The value to introduce in SPA depends on the configurated Type of the correspondent Alarm
.
If Independent Alarm Type, then SPA will be absolute value in physical units.
If Deviation Alarm Type, then SPA will be the deviated value of the band over oe under SP n.
If Deviation Band Alarm Type, then SPA will be the deviated value of the band on both sides of
SP n.
NOTE 2:
If the introduced value of any of the Alarm Setpoints SPA 1 to SPA 6, is higher than the
High or Low limits already set in the Configuration menu, this value will be displayed but when
validation key
is pressed, the value stored will be the High or Low preset value, depending
on the exceeded limit.
MODIFICATION OF HYSTERESIS OF THE ALARM SETPOINTS [HI 1...6]
- Press
repeatedly until the alarm to modify (
AL 1 to AL 6
) is displayed located in its
correspondent loop.
- Press
to go in the alarm. The display shows
[xxxx]
[SPA n]
where “n” is the alarm
number.
- Press
[0001]
[Hi n]
is displayed where “n” is the alarm number and [0001] indicates
0.1 or 1 depending on the physical units of the actual hysteresis value of the alarm.
NOTE:
The number of decimals should be the same as the one set for the Alarm.
- To modify the value press
and
until the new value of the hysteresis is achieved.
- To exit press
repeatedly , until
NORMAL DISPLAY.