ALARM SETPOINTS [AL 1] [AL 2] [AL 3] [AL 4] [AL 5] and [AL6]
Allow to see and modify the Alarm Setpoint value assigned to each loop.
The mnemonic AL could be visible, modifiable or hidden in the menu (by programming)
depending on number of active loops and the function assigned to each one of them.
Every instrument of the
HS-7000
Series is provided with 6 preconfigured Alarm Blocks.
The Alarm Blocks are independent of the physical relay outputs(slots Y1, Y2, Y3 and Y4) and
of the LED indicators on the display, and could be assigned on request by keypad or by
LoopWin(see Advanced Programming Manual). In the standard instruments, the configuration
is set as follows:
ALARM TYPES
THe instruments of the
HS-7000
Series are factory programmed as High or Low Alarm(see
figure below). Different alarm type can be programmed by keypad (see Alarm Configuration) or
by LoopWin software.
The predefined Alarm types are:
(a) Independent Hi-Alarm:
Activate the alarm when PV increases exceeding
AL value
(b) Independent Lo-Alarm:
Activate the alarm when PV decreases exceeding
AL value
The configurable Alarm types are:
(c) Deviation Hi-Alarm:
Activate the alarm when PV exceeds AL value over
the SP
(d) Deviation Lo-Alarm:
Activate the alarm when PV exceeds AL value under
the SP
(e) Band Deviation Alarm:
Activate the alarm when PV exceeds AL value on
both sides of SP
Any of those alarm types can be configured by
keypad (see Alarm Configuration) or by
LoopWin
software
.
(a)
(b)
(c)
(d)
(e)
SP
Control Setpoint
[SP]
SPA
Alarm Setpoint
[SPA]