RTU-CN01 Operation Manual
8-4
_8
Bit
Status
value
Indication
How to deal with
1
Extension modules connected to
RTU-CN01 are inconsistent with the
configuration data.
Redownload the configuration data to
RTU-CN01 by CANopen Builder.
bit2
0
No errors in special modules
--
1
Some error occurs in special modules. Check special modules.
bit3
0
Special modules works normally.
--
1
Special module offline
Check special modules and repower
RTU-CN01.
bit4
0
Valid configuration data
--
1
Invalid configuration data
Redownload the configuration data to
RTU-CN01 by CANopen Builder.
bit5
0
RTU-CN01 is working normally.
--
1
The work power for RTU-CN01 is
under voltage.
Check the power module for RTU-CN01.
bit6
0
RTU-CN01 is working normally.
--
1
RTU-CN01 detectes some
unrecognized special module.
Check if RTU-CN01 supports the special
module.
bit7
0
RTU-CN01 is working normally.
--
1
The number of special modules
connected to RTU-CN01 exceeds 8
units or the number of digital IO points
exceeds 128.
Remove the extra module.
bit8
0/1 Reserved
bit9
0
RTU-CN01 in RUN state
--
1
RTU-CN01 in STOP state
1. Check the state of the RUN/STOP switch of
RTU-CN01.
2. Check if H8000 was written to the control
word of RTU-CN01.
3. Check if there is any fatal error in RTU-CN01
Содержание RTU-CN01
Страница 11: ...RTU CN01 Operation Manual 2 6 _2 MEMO...
Страница 43: ...RTU CN01 Operation Manual 5 22 5 MEMO...
Страница 53: ...RTU CN01 Operation Manual 6 10 _6 MEMO...
Страница 68: ...Chapter 7 Application Examples 7 15 7_ Note Baud rate conversion 1 Mbps 1000 Kbps 1000000bps...
Страница 75: ...RTU CN01 Operation Manual 7 22 _7 The complete configuration of Send PDO mappings is as below...
Страница 85: ...RTU CN01 Operation Manual 8 6 _8 MEMO...
Страница 86: ...A 1 A Appendix A List of Accessories Table of Contents A 1 Accessories for CANopen Communication A 2...