Chapter 8 Error Diagnosis and Trouble-shooting
8-3
8_
RUN LED
LED status
Indication
How to correct
Green light ON RTU-CN01 in RUN state
--
Off
RTU-CN01 in STOP state
Turn the switch to RUN
Blinking
The setting of the node address
exceeds the allowed range.
Set the node address to a value between 1 and
127 by using the node address switch of
RTU-CN01
ALARM LED
LED status
Indication
How to correct
Off
RTU-CN01 works normally or
lacks the work power.
--
Red light blinking
1. The configuration data of
RTU-CN01 is invalid;
2. The extension modules on the
right of RTU-CN01 are in error
or fail to communicate with
RTU-CN01.
3. The setting of the node
address exceeds the allowed
range.
1. Check if downloading the RTU-CN01
configuration is normal and re-download the
RTU-CN01 configuration.
2. Check if the modules on the right side of the
RTU-CN01 are normal after obtaining relevant
diagnostic information via the CANopen Builder
software.
3. Set the node address to a value between 1 and
127 by using the node address switch of
RTU-CN01
Red light ON
1. Fatal errors or errors in the
configuration data of
RTU-CN01;
2. RTU-CN01 is under voltage.
1. Get relevant diagnostic information via the
CANopen Builder software.
2. Check the work power for RTU-CN01.
8.2
Status Word Diagnosis
The status word of RTU-CN01 is used to display the operating states of special modules and digital modules.
Refer to Section 5.2.3 to learn details about the use of status word.
Status word diagnosis:
Bit
Status
value
Indication
How to deal with
bit0
0
RTU-CN01 detected extension
modules.
--
1
RTU-CN01 failed to detect extension
modules.
1. Check if there are extension modules on the
right of RTU-CN01.
2. Repower RTU-CN01
bit1
0
Extension modules connected to
RTU-CN01 are consistent with the
configuration data.
--
Содержание RTU-CN01
Страница 11: ...RTU CN01 Operation Manual 2 6 _2 MEMO...
Страница 43: ...RTU CN01 Operation Manual 5 22 5 MEMO...
Страница 53: ...RTU CN01 Operation Manual 6 10 _6 MEMO...
Страница 68: ...Chapter 7 Application Examples 7 15 7_ Note Baud rate conversion 1 Mbps 1000 Kbps 1000000bps...
Страница 75: ...RTU CN01 Operation Manual 7 22 _7 The complete configuration of Send PDO mappings is as below...
Страница 85: ...RTU CN01 Operation Manual 8 6 _8 MEMO...
Страница 86: ...A 1 A Appendix A List of Accessories Table of Contents A 1 Accessories for CANopen Communication A 2...