Chapter 4 Installing and Wiring
4-5
4_
RTU-CN01 Safety Circuit Wiring
9
1
2
3
4
5
6
7
8
DVP-PS02
24V
0V
0V
24V
L
N
RTU CN01
-
L
N
AC power supply: 100
~
240VAC, 50/60Hz.
Power supply circuit protection fuse
System circuit isolation device: The electromagnetic contactor, relay and other switch can be used as
the isolation device to prevent the system from becoming unstable when the power supply is
discontinuous.
Power supply indicator
Emergency stop button: The button cuts off the system power supply when an accidental situation
takes place.
Delta power module DVP-PS02/24VDC
RTU-CN01 device
Ground
Safety circuit
4.4.2
Ground
The diameter of the ground should not be less than the diameters of the cables connected to the
terminals L and N.
If using multiple pieces of equipment, use a single-point ground.
RTU-CN01
Another piece
of equipment
The single-point ground is better.