Chapter 7 Application Examples
7-7
7_
10. With a double-click on “04DA” symbol, the “Special Module Configuration” dialog box
appears, where you select “Custom” as the work mode to reset the configuration of 04DA
module. Click on “OK” button to finish the configuration.
11. The “Digital Input/Output Points” interface appears by double-clicking on the symbol of
digital modules on the rightmost side of RTU-CN01. Click “OK” to finish the configuration.
By double-clicking “RTU-CN01” symbol, the “RTU Setting” dialog box appears. Refer to
Section 5.2.2 for details.