Turbo PMAC2 Related I-Variable Reference
Ixx95 is used only on power-on/reset or on the
$*
or
$$*
command. To get a new value of Ixx95 to take
effect, either the
$*
or
$$*
command must be issued, or the value must be stored to non-volatile flash
memory with the
SAVE
command, and the board must be reset.
Ixx95 is a 24-bit value; currently bits 16-23, which comprise the first two of six hex digits, are used.
Ixx95 is only used if Ixx10 is set to a non-zero value.
The possible values of Ixx95 and the absolute position feedback devices they reference are summarized in
the following table:
Ixx95 Value Range
Absolute Position Source
Ixx10 Address Type
Format
$000000 - $070000
ACC-8D Opt 7 R/D Converter
Multiplexer Port
Unsigned
$080000 - $300000
Parallel Data Y-Register
Turbo PMAC Memory-I/O Unsigned
$310000
ACC-28 A/D Converter
Turbo PMAC Memory-I/O Unsigned
$320000
ACC-49 Sanyo Abs. Encoder
Turbo PMAC Memory-I/O Unsigned
$480000 - $700000
Parallel Data X-Register
Turbo PMAC Memory-I/O Unsigned
$710000
ACC-8D Opt 9 Yaskawa Abs. Enc.
Multiplexer Port
Unsigned
$720000
MACRO Station Yaskawa Abs. Enc.
MACRO Node Number
Unsigned
$730000
MACRO Station R/D Converter
MACRO Node Number
Unsigned
$740000
MACRO Station Parallel Read MACRO
Node
Number
Unsigned
$800000 - $870000
Acc-8D Opt 7 R/D Converter
Multiplexer Port
Signed
$880000 - $B00000
Parallel Data Y-Register
Turbo PMAC Memory-I/O Signed
$B10000
ACC-28 A/D Converter
Turbo PMAC Memory-I/O Signed
$B20000
ACC-49 Sanyo Abs. Encoder
Turbo PMAC Memory-I/O Signed
$C80000 - $F00000
Parallel Data X-Register
Turbo PMAC Memory-I/O Signed
$F10000
ACC-8D Opt 9 Yaskawa Abs. Enc.
Multiplexer Port
Signed
$F20000
MACRO Station Yaskawa Abs. Enc.
MACRO Node Number
Signed
$F30000
MACRO Station R/D Converter
MACRO Node Number
Signed
$F40000
MACRO Station Parallel Read
MACRO Node Number
Signed
The following section provides details for Geo Macro Drive:
Parallel Data Read:
If Ixx95 contains a value from $080000 to $300000, from $480000 to $700000,
from $880000 to $B00000, or from $C80000 to $F00000, Motor xx will do a parallel data read of the
Turbo PMAC memory or I/O register at the address specified by Ixx10. It expects to find the least
significant bit of the feedback in Bit 0 of this register.
In this mode, bits 16 to 21 specify the number of bits to be read. If the last hex digit of Ixx95 is 0,
consecutive bits will be read from the address specified by Ixx81, with the least significant bit read from
bit 0. If the number of bits is greater than 24, the high bits are read from the register at the next higher-
numbered address. This format is used for registers and I/O devices with 24-bit interfaces.
If the last hex digit of Ixx95 is 4, 5, or 6, data will be read in byte-wide pieces, with the least significant
byte at the address specified in Ixx81, the next byte at one address higher, and so on, up to a possible 6
consecutive addresses. This format is intended for getting parallel data from the Acc-3E 3U-format stack
I/O board or the Acc-14E 3U-format pack (UMAC) I/O board, which have byte-wide interfaces. For this
format, the last hex digit of Ixx95 determines which byte of the 24-bit word is used, according to the
following table:
Ixx95 Last Digit
Byte
Bits
4
Low
0 – 7
5
Middle
8 – 15
6
High
16 – 23
In this mode, bits 16 to 21 of Ixx95 specify the number of bits to be read, starting with bit 0 at the
specified address. In this mode, they can take a value from $08 to $30 (8 to 48). If the number of bits is
greater than 24, the high bits are read from the register at the next higher-numbered address.
Содержание Geo MACRO
Страница 2: ......
Страница 6: ......
Страница 18: ...Geo MACRO Drive User Manual 6 Introduction...
Страница 26: ...Geo MACRO Drive User Manual 14 Specifications...
Страница 28: ...Geo MACRO Drive User Manual 16 Receiving and Unpacking...
Страница 78: ...Geo MACRO Drive User Manual 66 Software Setup...
Страница 88: ...Geo MACRO Drive User Manual 76 Setting Up Secondary Encoders...
Страница 90: ...Geo MACRO Drive User Manual 78 Setting Up Turbo PMAC Conversion Table...
Страница 110: ...Geo MACRO Drive User Manual 98 Setting Up Turbo Motor Operation...
Страница 130: ...Geo MACRO Drive User Manual 118 Troubleshooting...
Страница 175: ...Geo MACRO Drive User and Reference Manual Absolute Power On Online Commands 163...
Страница 176: ...Geo MACRO Drive User Manual 164 Useful Notes...
Страница 177: ...Geo MACRO Drive User and Reference Manual Appendix A 165...
Страница 182: ...Geo MACRO Drive User Manual 170 Appendix A Cable Drawings...
Страница 183: ...Geo MACRO Drive User and Reference Manual Appendix A 171...
Страница 184: ...Geo MACRO Drive User Manual 172 Appendix A...
Страница 185: ...Geo MACRO Drive User and Reference Manual Appendix A 173...
Страница 186: ...Geo MACRO Drive User Manual 174 Appendix A...
Страница 187: ...Geo MACRO Drive User and Reference Manual Appendix A 175...
Страница 191: ...Geo MACRO Drive User and Reference Manual Appendix A 179...
Страница 197: ...Geo MACRO Drive User and Reference Manual Appendix C 185...