6. Start the Putty application, from the Category navigation tree, select Serial,
and then configure the following options:
a. Speed (baud): 115200
b. Data bits: 8
c. Stop bits: 1
d. Parity: none
e. Flow control: none
7. Start the EXEC function by typing
enable
.
The password prompt appears.
8. Enter the password:
username admin password XXXXXXXXXXXX
(the default
The screen displays a message similar to the following:
The SupportAssist EULA acceptance option has not been
selected. SupportAssist
can be enabled once the SupportAssist EULA has been
accepted. Use the:
'support-assist activate' command to accept EULA and enable
SupportAssist.
DPappliance-switch#
9. From the switch CLI prompt, copy the switch configuration file by entering the
following command:
copy usbflash://< copy usbflash://<dell_sw_start_config>
startup-config >
The screen displays the following:
Please do not remove usbflash, until the operation completes!!
File with same name already exist.
Proceed to copy the file [confirm yes/no]:
10. Type "yes" to confirm that you want to copy the file.
The system copies the switch configuration from the USB drive to the switch.
11. When the system finishes copying the file, a message similar to the following is
displayed.
12067 bytes successfully copied
12. The switch must be re-loaded for the new configuration to take effect. Re-load
the switch by typing the command:
reload
The screen displays the following:
System configuration has been modified. Save? [yes/no]:
Dell S4048-ON Switch FRUs
DELL EMC CONFIDENTIAL
90
Integrated Data Protection Appliance (IDPA)
2.1
Field Replacement Guide