7.7 Tasks
7.7.1 Configure the terminal name
Configure the terminal name under
Configure > Input/output
.
PICUS automatically renames the terminal(s) when a function is selected. You can also rename the terminal(s):
1. Select
Rename
.
• Enter the new name:
2. Select
Save
.
INFO
Remember to
Write
when you have finished editing the input/output configuration.
7.7.2 Configure custom alarm(s)
AI
AO
PWM
DI
DO
Configurable for:
●
●
Analogue input (AI) custom alarms
INFO
The
Sensor
settings must be configured before configuring any AI custom alarms.
You can create up to 200 analogue custom alarms.
You can configure an analogue custom alarm with a
Set point
related to the y-axis (function input) for the sensor settings.
You can also configure analogue custom alarms for sensor failure as part of the sensor setup page.
Digital input (DI) custom alarms
Configure a digital input (DI) custom alarm for a
Low
or
High Trigger level
. The alarm is activated when the input is inactive
or active, respectively.