1. Select
Host
from the right side panel.
• A prompt is shown on screen:
2. Enter the host name or select a previously connected host from the available list.
3. Select
Connect
to connect to the host.
• PICUS attempts to log on with the same user name and password.
3.3.6 Connect all
To log on to ALL of the controllers listed.
1. Select
All
from the right side panel.
• PICUS attempts to log on with the same user name and password, if this is not possible you are prompted to confirm
alternative logon credentials.
3.3.7 Initial download (Initial DL)
Controllers supplied by DEIF contain the necessary application software pre-installed.
CAUTION
The
Initial DL
option is only to be used where the firmware update has NOT been applied correctly. In all other
situations the
Firmware
page should be used to apply new software.
See
Firmware
,
Introduction
in this document for more information about how to apply a new software upgrade.
If a firmware update has failed, the System status LED
on the PCM3.1 and the Internal communication status LED
on the PSM3.1 flash for more than one minute. In this situation, use
Initial DL
to attempt to apply the software to the
controller.
INFO
If
Initial DL
is used on a healthy system it does not apply any update or affect the running system.
To apply an initial download, perform the following steps:
PPM 300 PICUS manual 4189341080 UK
www.deif.com
Page 36 of 213