3. Add a
Normally open contact
and a
Normally open coil
to the logic grid and connect them to each other.
Add another
Normally open contact
and a
Normally open coil
to the logic grid and connect them to each
other.
4. Select the
normally open contact
in line 1.
a. Set the function to
ICC > Inputs > 5 > Inter-Controller Communication In 2
(where
5
is the Controller ID of the BUS
TIE breaker controller).
b. Select
Save
from the
Functions
menu.
5. Select the
normally open contact
in line 2.
a. Set the function to
ICC > Inputs > 5 > Inter-Controller Communication In 1
(where
5
is the Controller ID of the BUS
TIE breaker controller).
b. Select
Save
from the
Functions
menu.
6. Select the
normally open coil
in line 1.
a. Set the function to
Power management > Activate power management rule 1
.
b. Select
Save
from the
Functions
menu.
7. Select the
normally open coil
in line 2.
a. Set the function to
Power management > Activate power management rule 2
.
b. Select
Save
from the
Functions
menu.
8. Select
Write
from the right side panel.
9. Recommended: Enable
CustomLogic
on controller 1 before connecting to controller 2.
See
Enable CustomLogic
below.
GENSET controller 3:
1. Connect to GENSET controller 3.
2. Go to
Configure > CustomLogic > Logic creator
and create a
New
Project
with one
Section
and one
Block
.
3. Add a
Normally open contact
and a
Normally open coil
to the logic grid and connect them to each other.
PPM 300 PICUS manual 4189341080 UK
www.deif.com