3. Select
Write
from the right side panel.
Create the logic
1.
Go to
Configure > CustomLogic > Logic creator
and create a
New
Project
with one
Section
and one
Block
.
2.
Add a
Normally open contact
, a
Normally closed contact
, a
Timer
and two
Normally open coils
to the logic grid and connect them to each other. The normally open coils must be connected in parallel to each
other.
3.
Select the
normally open contact
. Set the function to
Mode > Inputs > Under switchboard control
.
4.
Select the
normally closed contact
.
a. Set the
Variable
to
B1
.
b. Select
Save
from the
Functions
menu.
5.
Select the
timer
.
a. Set the
Preset
to
10
.
b. Set the
Units
to
seconds
.
c. Select
Save
from the
Functions
menu.
6.
Select one of the
normally open coils
.
a. Set the function to
Outputs > Terminal(s) x, y, z, Slot #
. (The digital output configured in
Configure the output
,
step 2.)
b. Select
Save
from the
Functions
menu.
7.
Add a
Normally open contact
, a
Timer
and a
Normally open coil
to the logic grid and connect them
to each other.
PPM 300 PICUS manual 4189341080 UK
www.deif.com
Page 129 of 213