3.
Select the first
rising edge contact
.
a. Set the function to
Inputs > Terminal(s) x, y, z, Slot #
. (The first digital input configured in
Configure the output
,
step 2.)
b. Select
Save
from the
Functions
menu.
4.
Select the
timer
.
a. Set the
Mode
to
TP
(pulse timer).
b. Set the
Preset
to
10
.
c. Set the
Units
to
seconds
.
d. Select
Save
from the
Functions
menu.
5.
Select the second
rising edge contact
.
a. Set the function to
Inputs > Terminal(s) x, y, z, Slot #
. (The second digital input configured in
Configure the
output
, step 2.)
b. Select
Save
from the
Functions
menu.
6.
Select the
normally open coil
.
a. Set the function to
Engine > Start engine
.
b. Select
Save
from the
Functions
menu.
7.
Add a
Normally open contact
, a
Counter
, a
Normally open contact
, a
Normally open coil
, a
Normally open contact
and a
Normally closed contact
to the logic grid. Connect the elements
to each other on the logic grid as shown in the diagram below.
PPM 300 PICUS manual 4189341080 UK
www.deif.com
Page 139 of 213