8.
Select the
timer
.
a. Set the
ID
to
TM1
.
b. Set the
Preset
to
25
.
c. Set the
Units
to
100 milliseconds
. (Configuring steps 8b and 8c sets the timer to 2.5 seconds.)
d. Select
Save
from the
Functions
menu.
9.
Select the
normally open coil
.
a. Set the
Variable
to
B1
.
b. Select
Save
from the
Functions
menu.
10. Select
Write
from the right side panel.
Enable CustomLogic
1. Go to
Configure > Parameters
.
2. Enable
CustomLogic
under
Utility > CustomLogic
.
3. Select
Write
from the right side panel.
9.6 Advanced examples
9.6.1 Example 1: Activate an external component until push-button is pressed
Introduction
In this example CustomLogic is configured to activate an external component connected to a digital output on the controller if
there are no unacknowledged alarms.
The user starts the procedure by pressing push-button 1. The user then has 10 seconds to confirm the procedure with push-
button 2. If push-button 2 is pressed within the time limit and there are no unacknowledged alarms on the controller the digital
output is activated. The digital output remains active until the user presses push-button 3.
Logic restrictions
• If the user activates push-button 2 before the procedure is started, and keeps it activated while starting the procedure, the
digital output will not be enabled.
• If there is an unacknowledged alarm on the controller, the digital output will not activate.
• If the procedure has been started, the digital output can be enabled and disabled multiple times during the timer interval.
• If push-button 1 is pressed during the timer interval, the interval time will
not
be extended.
• If push-button 3 (to deactivate the external device) is activated when the digital output is enabled, the digital output will still
be enabled. The digital output is returned to not enabled after push-button is deactivated and activated again.