Safety input monitor outputs: Y4 to Y11
Y4 toY11 function as status monitoring of safety input devices connected to the SG-ONE.
Y4 is turned ON only in the case of teach mode is selected by mode select input.
Y5 is turned ON while both contacts of the safety device are ON. When 1 or more contacts are
OFF, the output is OFF.
Y6 to Y11 are turned ON while both contacts of the safety devices are ON. When both contacts of
the safety devices are OFF, the output is OFF.
If input monitor error is detected, pulses (1Hz) are transmitted.
Y4 outputs the status of safety input 1 (X0-T0, X1-T1).
Y5 outputs the status of safety input 2 (X2-T2, X3-T3).
Y6 outputs the status of safety input 3 (X4-T4, X5-T5).
Y7 outputs the status of safety input 4 (X6-T6, X7-T7).
Y10 outputs the status of safety input 5 (X10-T10, X11-T11).
Y11 outputs the status of safety input 6 (X12-T12, X13-T13)
●
Safety output monitoring outputs: Y12 and Y13
Y12 and Y13 function as monitoring outputs that output the status of the safety outputs. When the
safety outputs are OFF, the safety output monitor output is turned OFF immediately, even if
OFF-delay timer has been set.
Y12 outputs the status of safety output 1 (Y0 and Y1). This turns ON when Y0 and Y1 are both ON.
Y13 outputs the status of safety output 2 (Y2 and Y3). This turns ON when Y2 and Y3 are both ON.
●
State monitoring outputs: Y14 to Y16
Y14 to Y16 are monitoring outputs for the internal status of the SG-ONE.
Y14 turns ON when in Initial or Stop state.
Y15 turns ON in Initial, Protection or Configuration state.
Y16 turns ON when in Run state.
Refer to “Chapter 4 BASIC OPERATION”, or “Chapter 6 TROUBLESHOOTING”, for details of
each state.
Warning
Monitor outputs are not safety outputs. Do not use these to construct a safety system.
●
Solenoid outputs: Y17 and Y20
Y17 and Y20 are outputs for solenoid control that are used with a safety switch with a lock.
Teach mode: In Run state, when the safety outputs are ON, the solenoid outputs are ON.
Auto mode: In Run state, when the safety outputs are OFF and 1 or more safety inputs are OFF,
the solenoid outputs are turned ON. When all safety inputs are ON, the solenoid outputs are
turned OFF, although start input is not activated.
Warning
Solenoid outputs are not safety outputs. Do not use these to construct a safety system.
Caution
Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.
Содержание SG EASY One
Страница 1: ...Safety Control Unit INSTRUCTION MANUAL...
Страница 12: ...2 2 Dimensions 120 0 1 7 1 5 133 5 113 5 122 0 109 5 114 5 72 0 Locking hole Detail of locking hole...
Страница 34: ......
Страница 70: ...5 28 Using an DATALOGIC AUTOMATION light curtain SE series as S1 S2...
Страница 71: ...5 29 Timing chart Logic 3...
Страница 74: ...5 32 Logic circuit Logic 4...
Страница 80: ...5 38 Timing chart Logic 4...
Страница 81: ...5 39...
Страница 103: ...5 61 Operation example Logic 7 Machine running Machine stop danger zone A Movable guard A is opened...