5-100
Control start
This function confirms operation of the connected start input device. As shown in Fig.5-26, this
function is comprised of a functional input (I
n
) and a functional output (O
n
).
The start input (I
n
) ON operation is monitored to determine whether it is performed within the
designated control time (0.1 s to 5 s).
Fig. 5-26 Control start circuit
Description of operation
The operation timing is described in Fig. 5-27.
IIf the input turns ON within the designated control time (0.1 s to 5 s), the output turns ON until
the connected self-holding function or another trigger input turns ON. (The function output
turns OFF after the other trigger input turns ON.)
IIIf the input does not turn ON within the designated control time (0.1 s to 5 s) (If the function
input turns on before 0.1 s or after 5 s), the output does not turn ON.
Fig. 5-27 Operation timing of the control start function
I
n
O
Control
Start
Control