6.2.3 0-2* LCP Display
Parameters used to select what kind of information (e.g.
power, current, frequency) should be displayed in the
STATUS window.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in line 1,
left position.
[0]
None
No display value selected.
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
Present control word
[1603] Status Word
Present status word.
[1630] DC Link Voltage
Intermediate circuit voltage in the AFE.
[1634] Heatsink Temp.
Present heat sink temperature of the
AFE. The cut-out limit is 95
±
5
°
C;
cutting back in occurs at 70
±
5
°
C.
[1635] Inverter Thermal
Percentage load of the inverters.
[1636] Inv. Nom.
Current
Nominal current of the AFE.
[1637] Inv. Max. Current Maximum current of the AFE.
[1639] Control Card
Temp.
Temperature of the control card.
[1641] Current
Value of measured current
[1642] Voltage
Shows the actual mains voltage, when
the AFE is running.
[1643] Frequency
Returns the actual mains frequency,
when the AFE is running.
[1644] Power [kW]
Returns the calculated mains power in
kW
[1645] Power [hp]
Returns the calculated mains power in
HP.
[1660] Digital Input
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32 and 33).
Input 18 corresponds to the bit at the
far left. Signal low = 0; Signal high =
1.
[1665] Analog Output
42 [mA]
Shows the value at output 42 in mA.
[1666] Digital Output
[bin]
Binary value of all digital outputs.
[1671] Relay Output [bin Shows all the relay settings.
[1680] Fieldbus CTW 1
Control word (CTW) received from the
Bus Master.
[1682] Fieldbus REF 1
Main reference value sent with control
word from the Bus Master.
[1684] Comm. Option
STW
Extended fieldbus communication
option status word.
[1685] FC Port CTW 1
Control word (CTW) received from the
Bus Master.
[1686] FC Port REF 1
Status word (STW) sent to the Bus
Master.
[1690] Alarm Word
One or more alarms in a Hex code.
[1691] Alarm Word 2
One or more alarms in a Hex code.
0-20 Display Line 1.1 Small
Option:
Function:
[1692] Warning Word
One or more warnings in a Hex code.
[1693] Warning Word 2
One or more warnings in a Hex code.
[1694] Ext. Status Word
One or more status conditions in a
Hex code.
0-21 Display Line 1.2 Small
Option:
Function:
[1641]
*
Mains Current
[A]
Select a variable for display in line 1,
middle position. The options are the
same as listed for parameter group
0-2*
LCP Display
.
0-22 Display Line 1.3 Small
Option:
Function:
[1644]
*
Power [kW] Select a variable for display in line 1, right
position. The options are the same as listed
for parameter group
0-2* LCP Display
.
0-23 Display Line 2 Large
Option:
Function:
[1643]
*
Frequency [Hz] Select a variable for display in line 2.
The options are the same as those
listed for parameter group
0-2* LCP
Display
.
0-24 Display Line 3 Large
Option:
Function:
Select a variable for display in line 2.
[1630]
*
Counter [kWh]
The options are the same as those listed
for
0-20 Display Line 1.1 Small
.
0-25 My Personal Menu
Range:
Function:
Size
related
*
[0 -
9999]
Define up to 50 parameters to appear in the
Q1 Personal Menu
, accessible via the [Quick
Menu] key on the LCP. The parameters are
displayed in the
Q1 Personal Menu
in the
order they are programmed into this array
parameter. Delete parameters by setting the
value to ‘0000’.
For example, this can be used to provide
quick, simple access to just one or up to 50
parameters which require changing on a
regular basis (e.g. for plant maintenance
reasons) or by an OEM to enable simple
commissioning of their equipment.
How to Programme
Operating Instructions
MG33X402
Danfoss A/S © Rev. 05/2014 All rights reserved.
45
6
6