Alarm Word Extended Status Word
Bit Hex
Dec
Alarm Word
Alarm Word 2
Warning Word
Warning
Word 2
Extended
Status Word
31 80000000
2147483648
Extended Status Word
Table 6.8 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for diagnose.
See also
parameter 16-94 Ext. Status Word
WARNING 1, 10 Volts low
The 10 V voltage from terminal 50 on the control card is
below 10 V.
Remove some of the load from terminal 50, as the 10V
supply is overloaded. Max. 15 mA or minimum 590
Ω
.
WARNING 5, DC-link voltage high
The DC bus voltage is higher than the overvoltage limit of
the control system. The AFE is still active.
WARNING 6, DC link voltage low
The DC bus voltage is below the undervoltage limit of the
control system. The AFE is still active.
WARNING/ALARM 7, DC over voltage
If the DC bus voltage exceeds the limit, the AFE trips after
a time.
3 x 525-690 V
[V DC]
Undervoltage
553
Voltage warning low
585
Voltage warning high
1084
Overvoltage
1130
The voltages stated are the DC bus voltage of the AFE with a
tolerance of
±
5%.
Table 6.9 Alarm/Warning Limits
WARNING/ALARM 8, DC under voltage
If the DC bus voltage drops below the “voltage warning
low” limit (see
), the frequency converter checks if
24 V backup supply is connected.
If no 24 V backup supply is connected, the frequency
converter trips after a given time (depending on the unit).
To check whether the supply voltage matches the AFE, see
chapter 5.1 General Specifications
WARNING/ALARM 9, Inverter overloaded
The AFE is about to cut out because of an overload (too
high current for too long). The counter for electronic,
thermal protection gives a warning at 98% and trips at
100%, while giving an alarm. The AFE cannot be until the
counter is below 90%.
The fault is that the frequency converter is overloaded by
more than 100% for too long.
WARNING/ALARM 13, Over Current
The peak current limit (approx. 200% of the rated current)
is exceeded. The warning will last approx. 8-12 s, then the
AFE trips and issues an alarm.
ALARM 14, Earth fault
There is a discharge from the output phases to earth. Turn
off the AFE and remove the earth fault.
ALARM 15, Incomplete hardware
A fitted option is not handled by the present control board
(hardware or software).
ALARM 16, Short-circuit
There is short-circuiting in the outout phases.
Turn off the AFE and remove the short-circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the AFE.
The warning will only be active when
8-04 Control Word
Timeout Function
is NOT set to
OFF
.
Parameter 8-03 Control Word Timeout Time
could possibly
be increased.
WARNING/ALARM 21, Parameter error
The parameter is out of range. The parameter number is
reported in LCP. The affected parameter must be set to a
valid value.
WARNING 23, Internal fan fault
The fan warning function is an extra protection function
that checks if the fan is running/mounted. The fan warning
can be disabled in
14-53 Fan Monitor
(set to
[0] Disabled
).
WARNING 24, External fan fault
The fan warning function is an extra protection function
that checks if the fan is running/mounted. The fan warning
can be disabled in
14-53 Fan Monitor
(set to
[0] Disabled
).
ALARM 29, Heat sink temperature
The temperature of the AFE heat sink has exeeded the
limit.
P400; 110
°
C
P800/PIM2: 95
°
C
The temperature fault is cannot be reset untill the
temperature of the heat sink has dropped th a safe level.
P400: 95
°
C
P800/PIM2: 80
°
C
ALARM 33, Inrush fault
Too many power ups have occured within a short time
period. See the chapter
General Specifications
for the
allowed number of power ups within one minute.
WARNING/ALARM 34, Fieldbus communication fault
The fieldbus on the communication option card is not
working correctly. Please check parameters associated with
the module and make sure module is properly inserted in
How to Programme
Operating Instructions
MG33X402
Danfoss A/S © Rev. 05/2014 All rights reserved.
67
6
6