Bit
AFE Profile
Bit = 0
Bit = 1
0
Control not ready
Control ready
1
Unit not ready
Unit ready
2
Soft charge not
ready
Soft charge ready
3
No trip
Trip
4
-
-
5
-
-
6
No TripLock
TripLock
7
No warning
Warning
8
DC-link not on
reference
DC-link on reference
9
Local control
Remote control
10
Not ramping
Ramping
11
Not running
Running
12
-
-
13
No DC voltage
warning
DC voltage warning
14
No current limit
Current limit
15
No Thermal
warning
Thermal warning
Table 6.5 Bus Status Word
8-13 Configurable Status Word STW
Option:
Function:
Bit 12 to 15 of the STW is config-
urable for various status signals.
[0]
No function
[1]
*
Profile default
[2]
Alarm 68 only
[3]
Trip except Alarm 68
[16] T37 DI status
6.7.3 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
[0]
*
FC
Communication according to the FC Protocol as
described in the
VLT AutomationDrive Design Guide,
RS-485 Installation and Set-up
.
[1]
FC MC Select the protocol for the FC (standard) port.
8-31 Address
Range:
Function:
Size related
*
[ 1 - 255 ] Enter the address for the FC (standard)
port.
Valid range: 1-126.
8-32 FC Port Baud Rate
Option:
Function:
[0] 2400 Baud
Baud rate selection for the FC (standard) port.
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-35 Minimum Response Delay
Range:
Function:
10 ms
*
[ 1 - 10000
ms]
Specify the minimum delay time
between receiving a request and
transmitting a response. This is used for
overcoming modem turnaround delays.
8-36 Max Response Delay
Range:
Function:
Size
related
*
[ 11 -
10001 ms]
Specify the maximum permissible
delay time between transmitting a
request and receiving a response. If a
response from the frequency converter
is exceeding the time setting, then it is
discarded.
8-37 Max Inter-Char Delay
Range:
Function:
Size
related
*
[ 0.00 -
35.00 ms]
Specify the maximum permissible time
interval between receipt of 2 bytes.
This parameter activates time-out if
transmission is interrupted.
This parameter is active only when
8-30 Protocol
is set to
[1] FC MC
protocol.
Enables use of freely configurable telegrams or standard
telegrams for the FC port.
8-40 Telegram Selection
Option:
Function:
[1]
*
Standard Telegram 1
[101]
PPO 1
[102]
PPO 2
[103]
PPO 3
[104]
PPO 4
[105]
PPO 5
[106]
PPO 6
[107]
PPO 7
[108]
PPO 8
[200]
Custom telegram 1
How to Programme
Operating Instructions
MG33X402
Danfoss A/S © Rev. 05/2014 All rights reserved.
55