A trip is the action when an alarm has appeared. The trip will stop the AFE operation and change the digital output at
terminal 27 to Low, which will result in coasting the motor. It can be reset by pressing the reset button or make a reset by
a digital input (parameter group
5-1* Digital Inputs
[1]). The origin event that caused an alarm cannot damage the AFE or
cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause damage to AFE or connected
units. A Trip Lock situation can only be reset by a power cycling.
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Table 6.7 LED indication
Alarm Word Extended Status Word
Bit Hex
Dec
Alarm Word
Alarm Word 2
Warning Word
Warning
Word 2
Extended
Status Word
0
00000001
1
ServiceTrip, Read/
Write
reserved
Ramping
1
00000002
2
Heatsink temp. (A29) ServiceTrip,
(reserved)
Heatsink temp. (W29)
reserved
2
00000004
4
Earth Fault (A14)
ServiceTrip,
Typecode/
Sparepart
Earth Fault (W14)
reserved
3
00000008
8
Ctrl.Card Temp (A65) ServiceTrip,
(reserved)
Ctrl.Card Temp (W65)
reserved
4
00000010
16
Ctrl. Word TO (A17)
ServiceTrip,
(reserved)
Ctrl. Word TO (W17)
5
00000020
32
Over Current (A13)
reserved
Over Current (W13)
reserved
6
00000040
64
reserved
reserved
7
00000080
128
reserved
reserved
8
00000100
256
reserved
reserved
9
00000200
512
Inverter Overld. (A9) reserved
Inverter Overld (W9)
reserved
Power limit (W253)
10 00000400
1024
DC under Volt (A8)
reserved
DC under Volt (W8)
Regen limit (W252)
11 00000800
2048
DC over Volt (A7)
reserved
DC over Volt (W7)
12 00001000
4096
Short Circuit (A16)
reserved
DC Voltage Low (W6)
reserved
13 00002000
8192
Inrush Fault (A33)
reserved
DC Voltage High (W5)
14 00004000
16384
Mains ph. Loss (A4)
reserved
15 00008000
32768
reserved
16 00010000
65536
reserved
17 00020000
131072
Internal Fault (A38)
10V Low (W1)
Password Timelock
18 00040000
262144
Fans error
Fans Warn
Password Protection
19 00080000
524288
20 00100000
1048576
reserved
reserved
21 00200000
2097152
reserved
reserved
22 00400000
4194304
Fieldbus Fault (A34)
reserved
Fieldbus Fault (W34)
reserved
23 00800000
8388608
24 V Supply Low
(A47)
reserved
24V Supply Low (W47)
reserved
24 01000000
16777216
Mains Failure (A36)
reserved
Mains Failure (W36)
reserved
25 02000000
33554432
1.8V Supply Low
(A48)
reserved
Current Limit (W59)
reserved
26 04000000
67108864
reserved
Low Temp (W66)
reserved
27 08000000
134217728
reserved
Voltage Limit (W64)
reserved
28 10000000
268435456 Option Change (A67) reserved
reserved
29 20000000
536870912 AFE Initialized(A80)
Feedback Fault
(A61, A90)
Feedback Fault (W61,
W90)
30 40000000
1073741824 Safe Stop (A68)
How to Programme
Operating Instructions
66
Danfoss A/S © Rev. 05/2014 All rights reserved.