6.7.4 8-5* Digital/Bus
Parameters for configuring the control word digital/bus
merging.
NOTICE
These parameters are active only when
8-01 Control Site
is set to
[0] Digital and control word
.
8-53 Start Select
Option:
Function:
Allows a choice between controlling the Start
function via the terminals (digital input)
and/or via the bus.
NOTICE
This parameter is only active if
8-01 Control Site
is set to
[0] Digital and
control word
.
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
How to Programme
Operating Instructions
56