6.3 Parameters: 4-** Limits/Warnings
6.3.1 4-1* Limits
Use these parameters to adjust warning limits for power.
Warnings are shown on the LCP, can be programmed as
outputs, and can be read out via the serial bus in the
Extended Status Word.
4-18 Current Limit
Range:
Function:
Size related
*
[ 1.0 - 1000.0 %] This is a true current limit
function.
6.3.2 4-5* Adjustable Warnings
4-52 Warning Regen Limit
Range:
Function:
Size
related
*
[0-2*Nominal
NO Power kW]
Enter the regen power limit. When
the regenerative power exceeds
this limit the display reads Regen
Limit. The signal outputs can be
programmed to produce a status
signal on terminals 27 or 29 and
on relay outputs 01 or 02.
4-53 Warning Power Limit
Range:
Function:
Size
related
*
[0-2*Nominal
NO Power kW]
Enter the active power limit. When
the active power exceeds this limit
the display reads Power Limit. The
signal outputs can be programmed
to produce a status signal on
terminals 27 or 29 and on relay
outputs 01 or 02.
6.3.3 4-9* Output Limits
4-90 Output Frequency Deviation Function
Option:
Function:
Select the time-out function. The time-out
function activates when the output frequency
exceeds the deviation limit set in parameter
4-91
Output Frequency Deviation Limit
for the time set
in parameter
4-92 Output Frequency Deviation
Timeout
[0]
*
Trip
Generate an alarm trip when a fault condition is
encountered.
[1]
Warning Generate a warning when a fault condition is
encountered.
[2]
Disabled Take no action on fault condition.
Select which reaction the AFE should take in case the
frequency deviation set in parameter
4-91 Output Frequency
Deviation Limit
.
4-91 Output Frequency Deviation Limit
Range:
Function:
20%
*
[1 - 50%] Selects the max deviation in procentage from
the nominiel mains frequency set in parameter
40-01 Mains Frequency
4-92 Output Frequency Deviation Timeout
Range:
Function:
0.001 s
*
[0.000 - 60.000
s]
Selects the max time where the
frequency deviation set in parameter
4-91 Output Frequency Deviation Limit
can be exceeded.
4-93 Output Voltage Deviation Function
Option:
Function:
Select the time-out function. The time-out
function activates when the output vontage
exceeds the deviation limit set in parameter
4-91
Output Frequency Deviation Limit
for the time set
in parameter
4-92 Output Frequency Deviation
Timeout
.
[0]
*
Trip
Generate an alarm trip when a fault condition is
encountered.
[1]
Warning Generate a warning when a fault condition is
encountered.
[2]
Disabled Take no action on fault condition.
Select which reaction the AFE should take in case the
voltage deviation set in parameter
4-94 Output Voltage
Deviation Limit
is exeeded.
4-94 Output Voltage Deviation Limit
Range:
Function:
20%
*
[1 - 50%] Selects the max deviation in procentage from
the nominiel mains voltage set in parameter
40-00 Mains Voltage
.
4-95 Output Voltage Deviation Timeout
Range:
Function:
0.001 s
*
[0.000 - 60.000
s]
Selects the max time where the
voltage deviation set in parameter
4-94 Output Voltage Deviation Limit
can be exceeded.